Fault And Anomaly Signals - Immergas VICTRIX MAIOR 28 Instructions And Recommendations

Table of Contents

Advertisement

2.5 FAULT AND ANOMALY SIGNALS

The boiler signals any anomalies using a code shown on the boiler display (Fig. 52) according to the following table:
Error
Anomaly signalled
Code
No ignition block
01
Safety thermostat
function block (NTC
02
flow/return
overheating)
Flue safety thermostat
03
block
Contacts resistance
block/Damaged
04
hardware board
05
Delivery probe fault
06
DHW probe fault
Chimney sweep
07
function
(1) If the shutdown or fault persists, contact an authorised company (e.g. Authorised Service Centre)
(2) The anomaly can only be verified in the list of errors in the "Information" menu
(3) Error displayed only on CAR
(4) Error displayed only on Anomalies log
72
In the event of request of room central heating or domestic
hot water production, the boiler does not switch on within
the preset time. Upon appliance commissioning or after
extended downtime, it may be necessary to eliminate the
block.
During normal operation, if a fault causes excessive over-
heating internally, the boiler goes into overheating block.
During normal operation, if a fault causes excessive flue gas
overheating, the boiler blocks
The P.C.B. detects a fault on the gas valve supply. Check its
connection. (The fault is detected and displayed only in the
presence of a request). Upon confirming that the fault does
not concern the gas valve, you must replace the P.C.B. if the
fault does not disappear after pressing the Reset button.
The board detects an anomaly on the NTC flow probe.
Safety thermostat triggered.
The board detects an anomaly on the domestic hot water
NTC probe. In this case the antifreeze function is also in-
hibited
The boiler is in chimney sweep or calibration operation.
V2
Cause
Boiler status / Solution
Press the Reset button (1)
Press the Reset button (1)
Press the Reset button (1)
Press the Reset button (1)
The boiler does not start (1)
Press the Reset (1) button
In this case the boiler continues to
produce domestic hot water but not
with optimal performance (1)
(3)