8.4. Battery Specification
Table 8-4: Battery Specification
Battery Type
Battery Quantity
Battery Voltage
Recharge Profile
End of Discharge Voltage
Charge Current
Battery Start Option
Battery Environment
Note! For external battery connection, 48 Vdc Shunt release signal wiring from the UPS must be
connected to the auxiliary signal connection of the battery breaker.
8.5. UPS Environmental Specifications
Table 8-5: UPS Environmental Specifications
Ambient Service Temperature Range,
(UPS)
Ambient UPS Storage Temperature Range
Maximum Service Altitude
Relative Humidity Range
Acoustic Noise at 1 m
EMC
Copyright © 2022 Santak Corporation plc. All rights reserved.
VRLA, 12 Vdc
36-44 blocks, 216-264 cells per battery string, default 40 blocks
per battery string:
36 blocks, Module derating to 50kW
38 blocks, Module derating to 55kW
40 blocks, Module 60kW
Note! Battery strings with different battery quantity and
voltage may not be connected in parallel!
432V (36 blocks) to 528V (44 blocks)
ABM or float charge
1.67 VPC to 1.75 VPC, configurable or automatic
(load adaptive)
Configurable:
400kW 28A-280A configurable, default 175A @ 60% load;
500kW 32A-320A configurable, default 200A @ 60% load;
600kW 40A-400A configurable, default 250A @ 60% load;
Yes
Discharge: -20°C~ +50°C
Charging: 0°C~ +40°C
Storage: -15°C~ +40°C
Recommended working and storage temperature: +25°C
+0°C to +30°C (32°F ~ 86°F), No output power derating
required.
From -25°C to +55°C (-13°F ~ -131°F) in the protective
package*
Should UPS be intended for application above 2000m, contact
your service representative for important information about high
altitude operation.
5 to 95%, no condensation allowed
There shall be at least a 1.8°F (1.0°C) difference between the dry bulb
temperature and the wet bulb temperature, always, to maintain a non-
condensing environment.
At 1m per ISO 7779 standard
300kW : ≦ 74.6dB
600kW : ≦ 78.8dB
1200kW : ≦ 81.8 dB
Class: C3 (GB 7260.2 / IEC 62040-2)
3C3 HD 400-600 kVA UPS
Installation and Operation Manual
88