Table 3-8: Maximum Recommended Multi-Core Cable Sizes (Unit:mm 2 ); Table 3-9: Minimum Recommended Multi-Core Cable Sizes (Unit:mm 2 ); Table 3-10: Rated And Maximum Currents For Rated Power And Voltage (Unit:a) - Santak CASTLE Series User Manual

400-600kva ups
Hide thumbs Also See for CASTLE Series:
Table of Contents

Advertisement

The selection of wire diameter needs to take into account the future power upgrade of UPS.
Table 3-8: Maximum Recommended Multi-core Cable Sizes (unit:mm
UPS
power
input
400kW
3*150
500kW
3*150
600kW
3*240
*:The UPS busbars wiring needs to be evenly divided (see
needs to take into account the future power upgrade of UPS.
Table 3-9: Minimum Recommended Multi-core Cable Sizes (unit:mm
UPS
power
input
400kW
3*70
500kW
3*70
600kW
3*95
*:
The UPS busbars wiring needs to be evenly divided (see

Table 3-10: Rated and Maximum Currents for Rated Power and Voltage (unit:A)

power
380
400kW
665
500kW
791
600kW
950
NOTE
Bypass fuse type should be greater than 10 times rated I
Copyright © 2022 Santak Corporation plc. All rights reserved.
UPS
output
3*150
3*150
3*240
Figure 4-9
UPS
output
3*70
3*70
3*95
Figure 4-9
Input Current
400
415
631
609
752
725
905
870
Bypass
N*
input
3*150
5*150
3*150
5*150
3*240
5*240
to
Figure 4-15
for the location of the busbars).
Bypass
input
2*70
4*70
3*70
4*70
3*95
4*95
Figure 4-15
to
for the location of the busbars).
Output current
380
400
638
606
760
722
915
870
2
t 20ms.
3C3 HD 400-600 kVA UPS
Installation and Operation Manual
2
)
Battery*
5*150
5*150
4*240
The selection of wire diameter
2
)
N*
Battery*
4*70
4*70
5*95
Battery
(Rated)
415
584
911
696
1085
835
1302
PE*
8*150
8*150
6*240
PE*
6*70
6*70
6*95
Battery
(Max)
1094
1302
1563
24