7.1 Single phase input Tower model Specification

ARES PLUS
Nominal power
Input system
Nominal voltage
Frequency
AC
Voltage range
Input
Frequency range
Input power factor
Bypass Voltage Range
Nominal Voltage
Battery Capacity &
Quantity
Backup Time
Battery
Input
Battery charger time
Output wiring system
Inverter Mode
Output voltage
Waveform
Harmonic Distortion
AC
Output frequency
Output
Overload capability
Transfer time
Line Mode
Efficiency
Battery Mode
Interface
Alarm Function
Protection Function
Noise
1. Subject to safety regulation and rating of power cord/socket, output power might need derating, find detail on the
product label
2. Subject to change according to order, check the product name plate for specified battery voltage information.

Chapter 7 Specification

ECO1000
1000VA/900W
24V
12V/7AH
x 2pcs
Charger to 90% battery capacity in 5 hours (standard) Dependent on the capacity of external
88%
85%
AC/DC input under abnormal, overload condition and Inverter problems
AC input or output above or below the range of voltage, overload, over temperature
ECO2000
2000VA/1800W
Single phase (L/N+PE)
LV: 100/110/120/125Vac
50/60Hz
LV: 65~145VAC±5VAC
(40~70)±0.5Hz
>0.99
LV:95~130V/ (75~145Vac max)
48V
12V/7AH
x 4pcs
Half loaded ≥8 minutes,
Full loaded ≥3 minutes (standard)
batteries (long backup time)
Single phase (L/N+PE)
LV:100/110/120/125Vac
Sine Wave
THD<2% (linear load)
50/60±4Hz (Sync mode)
50/60Hz±1% (Fix Freq. mode)
105~125%≥ 60s,126~150%≥30s The recover point is 70%
Battery <-> Line Mode: 0 ms
89%
86%
RS232, USB, Intelligent Slot, EPO, ROO
and short circuit protection
<50dB
35
ECO3000
3000VA/2700W
72V
12V/7AH
x 6pcs
90%
87%