3.3.2 Output Wiring
The input of the equipment needs to be protected by UPS should connect to the UPS output.
Outlet and terminal block are available for output connection from UPS, with refer to figure
in section 2.3.2:
Model
Rating Capacity
1K
1kVA
2K
2kVA
3K
3kVA
Please find rated output capacity of product , avoid overload and used wire with sufficient current
rating, with refer to below table.
Model
1K
2K
3K
Procedure for output wiring:
1. Plug the AC input cord of the equipment needs UPS protection to the Outlet of the UPS.
2. To connect more equipment than available Outlet number, please use extension cord, connect
3. to the Outlet or output terminal block, mind the total consumption current must not exceed rated
4. current capacity of the product.
5. The output terminal is protected by a cover, uncover the terminal , use appropriate connecting
Quantity of output
socket
4 x NEMA5-15R
4 x NEMA5-15R
+2 x NEMA5-20R
4 x NEMA5-15R
+4 x NEMA5-20R
Nominal Output
Voltage
100/110/120/125
Vac
Output terminal block & wiring
cable AWG/Cross-section Area
14 AWG for TB output L/N
12 AWG for bonding
Use 75℃ copper wire
10 AWG for output L/N
10 AWG for bonding
Use 75℃ copper wire
Rated output Current
9.0/9.1/8.4/8.1A
18.0/18.1/16.6/16.0A
24.4/24.5/25/24A
16
Terminal Block
Tightening Torque
NA
0.5 Nm (4.4 Lb. In)
Wire for terminal
2
>14 AWG/2mm
Use 75℃ copper
wire
2
>12AWG/4mm
Use 75℃ copper
wire
NA
Tightening
Torque
0.5Nm
(4.4 Lb In)