Assa Abloy SARGENT SN Sereis Installation Instructions Manual page 8

Bored lock

Advertisement

Wiring Diagrams (Continued)
5
SN200 Wiegand UL294/TAMPER Configuration Application Diagram #1
Tamper will trigger when reader is removed from door and tamper wiring is connected at the panel.
Reader*
Actuator
*Maximum AVG - RMS current draw during continuous card reads
Not evaluated by UL.
Peak - highest instantaneous current draw during RF communication
Reader Electronics Requires 12VDC Filtered and Regulated
12 Conductor
ElectroLynx Harness
From McKinney
SN200
*IMPORTANT: Pin 7 must be tied to earth ground in the access
control panel.
Wiring in accordance with the NEC, ANSI/NFPA 70
Fail secure installations are subject to approval of local AHJ
Fail secure installations shall permit use of Listed panic
hardware to allow emergancy exit from the protected area.
Failure to follow proper ESD safe grounding procedures could
lead to equipment failure.
*UL294 is a United States based standard.
12/24VDC System
12V
Average
Peak
Average
75mA
250mA
n/a
500mA
500mA
250mA
QC12 Electric
Hinge From
READER NEG - Black, 1
McKinney
READER POS - Red, 2
DATA_1 - White, 3
DATA_0 - Green, 4
RX (NO) - Orange, 5
RX (COM) - Blue, 6
*EARTH GROUND - Brown, 7
TAMPER - Yellow, 8
LOCK NEG - Violet, 9
LOCK POS - Gray, 10
DPS (NC) - Pink, 11
DPS (COM) - Tan, 12
8
SN200/210 Bored Lock
24V
Peak
n/a
250mA
H N G
120 VAC
12-24VDC
12VDC
Input
-
+
-
+
(-)
12VDC
(+)
DATA_1
DATA_0
RX (NO)
RX (COM)
DPS
DPS
5VDC
Input
nection (+)
Unsupervised Open
Input
nection (-)
Collector Tamper
A8282B • 800-810-WIRE (9473) • www.sargentlock.com
Power Supply
(By Others)
Electrical
Access
Control
Panel
(By Others)
Use (NC) for
Fail Safe
Operation
Lock
Relay
(NO) Fail
Secure
Operation
Panel Circuitry
1KΩ
Con-
1KΩ
A to D Converter
Con-
1KΩ