Battery Storage And Recharge - Huawei LUNA2000-5-S0 User Manual

Hide thumbs Also See for LUNA2000-5-S0:
Table of Contents

Advertisement

LUNA2000-(5-30)-S0
User Manual
Alarm
Alarm Name
ID
3051
ESS Version Mismatch
3061
Battery Pack Lifespan
Reached

8.4 Battery Storage and Recharge

Battery Acceptance Inspection
A battery recharge label must be put on the battery packing case. The recharge
label should contain the latest charge time and the next recharge time.
Battery Storage Requirements
1.
2.
3.
4.
Issue 15 (2024-01-12)
Alarm
Severity
Major
Major
Place batteries according to the signs on the packing case during storage. Do
not put batteries upside down or sidelong.
Stack battery packing cases by complying with the stacking requirements on
the external package.
Handle batteries with caution to avoid damage.
The storage environment requirements are as follows:
Ambient temperature: -10–55°C; recommended storage temperature: 20–
30°C
Relative humidity: 5% to 80%
Place batteries in a dry and clean place with proper ventilation.
Place batteries in a place that is away from corrosive organic solvents and
gases.
Keep batteries away from direct sunlight.
Copyright © Huawei Digital Power Technologies Co., Ltd.
Possible Cause
1. The version of the
battery power control
modules does not
match that of the
battery packs, which
affects the normal
operation.
2. The update failed.
The battery has
reached its lifespan.
8 System Maintenance
Troubleshooting
1. The version of the
power control
modules in [Battery-
CabinetNo] does not
match that of the
battery packs and
needs to be updated.
2. If the update fails
multiple times,
contact your dealer or
technical support.
The battery has
reached the end of its
lifespan. Contact the
local recycling agency
to dispose of it in
compliance with local
laws and regulations
as well as applicable
standards.
129

Advertisement

Table of Contents
loading

This manual is also suitable for:

Luna2000-30-s0

Table of Contents