Technical Data

Auxiliary voltage
Voltage supply via extended range power supply unit
DC voltage
Rated auxiliary voltage U
Perm. voltage range
Power input
Permissible AC ripple voltage,
Peak to peak
Stored energy time in the event of power
failure / short circuit of the auxiliary voltage
AC voltage
Nominal power supply alternating voltage
U
~
H
Perm. voltage range
Power input
Alarm relay (GOK / DR)
Contact
Switching capability
Switching voltage
Permissible current per contact
Interface to the protection device
Optical fibre
– Fibre-optic plug type
– Optical wavelength
– Laser class 1 acc. to EN 60825–1/ –2
– Permissible optical link signal
attenuation
– Maximum transmission distance
54
H
1 changeover contact
MAKE
1000 W/VA
BREAK
30 VA
40 W resistive
250 V
5 A continuous
30 A for 0.5 s
ST–plug
λ = 820 nm
for use of FO 62.5/125 µm
max. 8 dB using glass fibre 62.5/125 µm
1.5 km (1 mile)
24 V– to 250 V–
19 V– to 300 V–
approx. 3.5 W
≤ 12 % at rated voltage, IEC 60255–11
≥ 50 ms
115 V~ to 250 V~, 50/60 Hz
92 V~ to 286 V~
approx. 3.5 VA
C53000-B1174-C151-1