When using the supply air heater, the supply air sensor (TJ) must be installed downstream the heater (or cooler) at the length
of sensor cable allows or up to the first branching or bend of air transportation system.
Only heaters with up to 0.6 kW power circuit can be connected directly to the control board. The heaters of higher power heaters must be con-
nected to separate electric power circuit.

8.1.3. VERSION S300

SMARTY air handling units are able to control one heater or preheater coil at a time. When the preheater is used, one more temperature sensor
has to be installed to the system. After connection, configuration has to be performed. For more information see section "ACCESSORIES SETUP
(VERSION S300)".

8.1.3.1. HEATER

0
In order to use a heating coil, following signals are required to be connected to the control board:
1. Electric heating coil command;
2. Heating coil overtemperature detector;
3. Heating coil position signal.
Output digital relays 24-230 V AC, max 6.3A, normally open/closed
NOTE: Power supply for the heater is not shown.
Heater Installation Diagram
Output digital relays 24-230 V AC, max 6.3A, normally open/closed
Electric heater must be installed inside the air duct. The layout is based on airflow direction ELECTRIC HEATER > SUPPLY AIR SENSOR (TJ).
When using the supply air heater, the supply air sensor (TJ) must be installed downstream the heater (or cooler) at the length
of sensor cable allows or up to the first branching or bend of air transportation system.

8.1.3.2. PREHEATER

In order to use a preheating coil, following signals are required to be connected to the control board:
1. Electric preheating coil command;
2. Air temperature after preheating coil;
3. Preheating coil overtemperature detector;
4. Preheating coil position signal.
Modification
Date
36
| EN
KE
TJ
Mini MCB
1
2
4
3
2
1
T7
Q13
Q14
Electric heating coil command
Figure 8.1.3.1.1.
4
3
2
1
T7
Q13
Q14
1
Electric preheating coil command
KE
TJ
Input Digital/NTC10k
Siemens S300
(in reference to GND)
Mini MCB
8
7
6
5
4
3
2
1
T2
X3
Preheating coil overtemperature detector
Date
2022-01-13
EPLAN
Ed.
justasbalsys
Project template with identification structure in accordance with IEC standard: Page structure with higher-level function and mounting location
Appr.
Name
Original
Replacement of
TJ
3
Heater
Input Digital/NTC10k
(in reference to GND)
7
6
5
4
3
2
1
T1
X8
Heating coil overtemperature detector
Signals for electrical heater
Preheater
Input Digital/NTC10k
(in reference to GND)
7
6
5
4
3
2
1
T1
TJ
X8
Air temperature sensor after preheating coil
Input Digital/NTC10k
(in reference to GND)
7
6
5
4
3
2
1
T1
B1
Outside air temperature sensor
Replaced by
EKA
4
5
Output 0-10V
6
5
4
3
2
1
T18
A3
GND
Heating coil position
Output 0-10V
6
5
4
3
2
1
T18
A3
GND
KE1
Preheating coil position
EPLAN Software & Service
Heater/preheater
GmbH & Co. KG
SMARTY v2023.2