Filters Maintenance; Heat Exchanger Maintenance - Salda SMARTY XP Mounting And Installation Instruction

Table of Contents

Advertisement

Figure 6.3.2.
Smarty 3X P / 4X P
6.4.

FILTERS MAINTENANCE

• In order to remove the filters, open filter cover by pulling the strap and take out the filters. Use Coarse 65% filters or optionally the ePM1 70%
filter for outdoor air filtration and the Coarse 65% filter for the exhaust air filtration.
• Dirty filters increase air resistance, this decreases the airflow into the rooms.
Figure 6.4.1.
Smarty XP
After changing the filters, please reset the filters timer. The instruction on reloading is provided in the particular unit's control
environment's documentation.
Operation of the unit without filters is not allowed.
Change the filters every 3-4 months or according to the notification on the control device.
6.5.

HEAT EXCHANGER MAINTENANCE

• Proceed to maintenance and repair after any rotation in the fan stopped.
• Clean the heat exchanger once per year.
• Prior to any maintenance, carefully remove the heat exchanger cassette. Submerge it in a bath and wash with warm soapy water (do not use
soda). Then flush it under a small jet of hot water (too fast jet of water may cause folding of the plates). Install the heat exchanger back only
when it is completely dry.
NOTE. Prior to performing steps in Figure 6.5.1 / Figure 6.5.2, steps in Figure 6.3.1 should be carried out.
SMARTY v2023.2
Figure 6.3.3.
Smarty 2X V
Figure 6.4.2.
Smarty 2X V
Figure 6.5.1.
Smarty 2X P
Figure 6.5.2.
Smarty 2X P E
Figure 6.3.4.
Smarty 3X V / 4X V
Figure 6.4.3.
Smarty 3X V / 4X V
EN |
23

Advertisement

Table of Contents
loading

Table of Contents