SMARTY R V
EN
MOUNTING AND INSTALLATION INSTRUCTION

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the SMARTY R V and is the answer not in the manual?

Questions and answers

Summary of Contents for Salda SMARTY R V

  • Page 1 SMARTY R V MOUNTING AND INSTALLATION INSTRUCTION...
  • Page 2: Table Of Contents

    1. CONTENTS 2. SYMBOLS AND MARKING 3. SAFETY INSTRUCTIONS AND PRECAUTIONS 4. INFORMATION ABOUT THE PRODUCT 4.1. DESCRIPTION 4.2. DIMENSIONS AND WEIGHT 4.3. TECHNICAL DATA 4.3.1. AIR FLOW DIAGRAMS 4.4. OPERATING CONDITIONS 4.5. STANDARD PACKAGE OF COMPONENTS 4.6. DESCRIPTION OF COMPONENTS 4.7.
  • Page 3 7.4.9. HOLIDAY SCHEDULE 7.4.10. WINTER/SUMMER MODE 7.4.11. DRYNESS PROTECTION 7.4.12. NIGHT COOLING FUNCTION 7.4.13. CO REDUCTION FUNCTION 7.4.14. FILTER PROTECTIONS 7.4.15. SYSTEM MODE COMMUNICATION WITH EXTERNAL CONTACTOR 7.4.16. FAN SPEEDS FROM AN EXTERNAL SYSTEM CONTACTOR 7.4.17. HEAT EXCHANGER CONTROL 7.4.18. SYSTEM MONITORING 7.4.19.
  • Page 4: Symbols And Marking

    2. SYMBOLS AND MARKING Stick the auxiliary label on the unit (on an easily accessible place) or on the dashed place of a technical manual in order to keep the important information about the unit. LN: XX000000 2019.01.01 Figure 2.1 - Technical label 1 - Logo;...
  • Page 5: Information About The Product

    In exceptional cases harmful gases could be drawn out of the chimney or extraction ducting back LQWR WKH URRP ,Q WKLV FDVH ZH VWULFWO\ UHFRPPHQG WR WXUQ R Salda Antifrost and use an external preheater for heat exchanger anti-frost protection (see Salda Antifrost function on the Remote controller manual).
  • Page 6 - power/current [kW/A] 0,006/0,1 0,006/0,02 WKHUPDO H FLHQF\ XS WR Heater - power/current [kW/A] 0,6/2,61 0,6/2,61 Exhaust air fan - phase/voltage [f/VAC/Hz] ~1/230/50 ~1/230/50 - power/current [kW/A] 0,07/0,6 0,084/0,75 - speed [min 1380 3200 - protection class IP44 IP54 - control imput [VDC] 0-10 0-10...
  • Page 7: Air Flow Diagrams

    4.3.1. AIR FLOW DIAGRAMS Performance Power consumption SMARTY 2R VER SMARTY 2R VER PLUS Supply air Supply air Exhaust air Exhaust air 7HPSHUDWXUH H FLHQF\ 7HPSHUDWXUH H FLHQF\ 7HPSHUDWXUH H FLHQF\ EDODQFHG PDVV ÀRZ  ([WUDFW DLU   ƒ&   4.4.
  • Page 8: Standard Package Of Components

    +40 C +5 C +40 C +40 C -23 C +15 C Figure 5.4.1 - operating conditions 4.5. STANDARD PACKAGE OF COMPONENTS 6WDQGDUG SDFNDJH ZLWKRXW RSWLRQDO DFFHVVRULHV LQFOXGHV • Mounting brackets (mural and unit parts), Rubber seal for vibration damping. •...
  • Page 9: Instalation

    Rotor box belt Rotor belt GNG00062 Smarty 2R VE door Door GNG00061 Rotor box motor Rotor motor ZVAR0133 GPUVRA009 (Smarty 2R VER) Fan supply/exhaust GVESMARTY001 (Smarty 2R VER plus) Rotor box Rotor box GPURSD085_330 Temperature sensor 3 m PJUT0063 Temperature sensor 1,5 m TL/TA PJUT0062 Controler...
  • Page 10: Unpacking

    5.3. UNPACKING 5.4. MOUNTING DIAGRAM Figure 5.4.1 - Smarty RV (** Only one sensor can be used at a time) Figure 5.4.2 - Indication for duct connection. Figure 5.4.3 - Ventilated premises Figure 5.4.4 - Air from cooing hood LIST OF COMPONENTS Plate heat exchanger Fire alarm damper actuator I Supply air fan...
  • Page 11: Mounting

    POSSIBLE PCB INPUTS/OUTPUTS Fire alarm Working indication output Fireplace protection Alarm indication output System mode switch (START/STOP) Fans speed switch (BOOST) * Compone 5.5. MOUNTING • ,QVWDOODWLRQ VKRXOG RQO\ EH SHUIRUPHG E\ TXDOL¿HG DQG WUDLQHG VWD  • When connecting air ducts, consider the notices indicated on the casing of the unit. •...
  • Page 12: Connection Of Air Ducts

    5.5.3. CONNECTION OF AIR DUCTS ‡ &RQQHFWHG DLU GXFWV PXVW EH VWUDLJKW DQG KDYH WKHLU RZQ ¿[LQJ • Make sure that the fans can not be accessed through air duct heads. If it is possible to access the fan, protective grid should be installed. You can choose it in our website.
  • Page 13: Shield Installation

    Use cooker hood supplied by our company only. Equipment is not tested with other cooker hoods and company holds no responsibility for malfunction or failures of the equipment in this case. 5.5.6. SHIELD INSTALLATION 5.6. CONNECTION OF THE UNIT TO ELECTRIC NETWORK •...
  • Page 14: Pre-Startup Recomendations Of The Unit (In The Presence Of The Enduser)

    5.7.2. PRE-STARTUP RECOMENDATIONS OF THE UNIT (IN THE PRESENCE OF THE ENDUSER) 3ULRU WR VWDUWXS WKH V\VWHP PXVW EH WKRURXJKO\ FOHDQHG &KHFN ZKHWKHU • operation systems and unit elements as well as automation and automation devices were not damaged during installation, ‡...
  • Page 15: Filters Maintenance

    • 5HPRYH WKH ¿OWHU &KDQJLQJ ¿OWHUV ¿OWHUV UHORDG WLPHU FRQWURO 'HVFULSWLRQ RI UHPRWH FRQWURO SDQHO IXQFWLRQV LV SURYLGHG LQ WKH UHPRWH FRQWURO panel technical documentation or on the website www.salda.lt. $OORZHG WR RSHUDWH WKH XQLW ZLWKRXW ¿OWHUV ,W LV UHFRPPHQGHG WR FKDQJH WKH ¿OWHUV HYHU\  PRQWKV RU LQ DFFRUGDQFH WR ¿OWHU WLPHU 6.4.
  • Page 16: Heater Maintenance

    Figure 6.4.2 - Smarty 2R VER plus Be sure the unit is disconnected from power source before performing any maintenance or repair. 6.5. HEATER MAINTENANCE • (OHFWULFDO KHDWHU GRHV QRW QHHG WR EH VHUYLFHG DGGLWLRQDOO\ ,W LV FRPSXOVRU\ WR FKDQJH ¿ OWHUV DV GHVFULEHG DERYH •...
  • Page 17: Control

    Ventilation unit can be controlled using a remote control, web interface via MB-Gateway and building management system. More information about the possibilities of controlling is provided in the table below. MB-Gateway + WIFI + SALDA AIR app Stouch FLEX MCB...
  • Page 18: Description Of The Units Functions

    The following control board functions can be fully con trolled only with SA-Control remote con trol panel, MB-Gateway web application or SALDA AIR app. In case of Stouch remote con trol panel use the description of remote control panel functions for MCB control board.
  • Page 19: System Control

    In Stand-by mode the system is shut down for a permissible period (based on the Stand-by mode blocking function settings). The Building protection mode is designed to protect premises against moisture accumulation. The system operates at speed 1. Based on manufacturer’s parameters (by default) this mode controls the temperature (the desirable one is indicated), but, if necessary, it can EH VZLWFKHG R  LH WR DFWLYDWH WKH HQHUJ\ VDYLQJ PRGH $OVR LI QHFHVVDU\ IXOO UHFLUFXODWLRQ IXQFWLRQ LV DFWLYDWHG ADJUSTER ›...
  • Page 20: System States

    7.4.3. SYSTEM STATES 7KLV ¿HOG LQIRUPV D XVHU DERXW WKH H[LVWLQJ V\VWHP VWDWH ,W LV GLVSOD\HG LQ WKH PDLQ ZLQGRZ ADJUSTER › VENTILATION CONTROL or the main window of the user environment. The table below shows possible system states. SYSTEM STATE DESCRIPTION Stand-by mode System operates in Stand-by mode...
  • Page 21: Fan Control

    between the elements. 7.4.6. FAN CONTROL 7KH SUHIHUUHG DLUÀRZ FDQ EH LQGLFDWHG LQ SHUFHQWDJH RU LQ  ¿[HG VSHHGV ZKHUH HDFK RI WKHP LV GHGLFDWHG WR D UHOHYDQW V\VWHP PRGH • Building protection; • Economy; • Comfort; • Maximum power. )DQ VSHHG FDQ EH FRQWUROOHG E\ •...
  • Page 22: Night Cooling Function

    7.4.12. NIGHT COOLING FUNCTION This function is designed to save energy in the morning, when a fresh night air is used to cool down the building. The function is active only in VXPPHU ,I LW LV VZLWFKHG RQ EXW QRW DFWLYH \HW DFWLYDWLRQ FRQGLWLRQV DUH FKHFNHG •...
  • Page 23: Heat Exchanger Control

    7.4.17. HEAT EXCHANGER CONTROL Cold - Heat Recuperation &ROGKHDW UHFRYHU\ IXQFWLRQ LV GHVLJQHG WR FRQWURO D KHDW H[FKDQJHU ,WV SRZHU LV FRQWUROOHG E\ • Using plate heat exchanger - bypass damper. When it is closed, the heat exchanger is operating at full capacity. Its power is reduced by open- ing the damper.
  • Page 24: Changing Passwords

    This can be useful, if you need to check if everything is properly connected. Moreover, in the event of failure, certain components can be activated so that the unit operates irrespective of sensors and protections. Of course, this method should be applied in exceptional cases until the failure LV UHFWL¿HG If the service environment window SERVICE ›...
  • Page 25: Event Log (History)

    the table below. INDICATION ALARMS LIST INDICATION ALARMS LIST Alarm! Controller cabinet temperature sensor fail- Z. $. Warning! Rotor broken belt alarm ure. System stopped $. Z. Alarm! Fireplace protection activated Fire damper test OK Z. Z. Warning! Dryness protection activated Warning! Fire damper test failed Warning! Plate heat exchanger frost protection Z....
  • Page 26: System Versions And Running Time

    7.4.27. SYSTEM VERSIONS AND RUNNING TIME In the section ADJUSTER › USER SETTINGS › ABOUT \RX PD\ VHH VRIWZDUH DQG FRQ¿JXUDWLRQ YHUVLRQV WKDW DUH VDYHG LQ WKH SURGXFWLRQ OLQH QDPHO\ WR HYHU\ XQLW Next to them the running time since the unit has been manufactured is also displayed. It is calculated when the fans are rotating. 8.
  • Page 27: Connection Fo Accessories

    8.1. CONNECTION FO ACCESSORIES 8.1.1. SCHEMATIC OF CONTROLLER CONNECTIONS IN MCB Connector Contact No. Contact name Dunctional block name MCB FDI TACHO K_1(GND) Supply fan speed (RPM) MCB FDI TACHO A_1(+10V) MCB FDI TACHO K_2(GND) Extract fan speed (RPM) MCB FDI TACHO A_2(+10V) SMARTY RV v2019.12 EN |...
  • Page 28 Rotor speed (RPM)/ Too high condensation (NO) +24VDC MCB HOLO Supply air electrical heater automatic protection (NC)/ MCB DI1 Supply air Hydronic cooler heating/cooling changeover thermo- stat (NC/NO)/Water heater circulation pump fail +12VDC MCB DI2 Supply air electrical heater manual protection/ +12VDC Water heater protection (thermostat) (NC) MCB DI3...
  • Page 29: Sensor Or Connection Of Humidity Sensor Rh

    MCB PE MCB GND Recirculation damper control 3P MCB RECIRC_+24VDC_OPEN (DO4) MCB RECIRC_+24VDC_CLOSE (DO5) MCB PE MCB GND By-pass damper control 3P MCB BYPASS_+24VDC_OPEN (DO2) MCB BYPASS_+24VDC_CLOSE (DO3) 24VDC Power supply for water heater actuator +24VDC +24VDC STEP_B/ STEP_B By-pass step motor control STEP_A/ STEP_A +24VDC...
  • Page 30: Room Co Transmitter Installation Recommendation

    Electric installation: RH sensor of the extracted air is used to calculate the freezing point In order to reduce the CO concentration in the premise (-s), it is necessary to connect CO converter (canal or installed in the premises). 3XUSRVH RI WKH FRQQHFWRUV FRQWDFWV MCB: ; ±...
  • Page 31: Co Concentration According To Pettenkofer Limit

    8.1.4. CO CONCENTRATION ACCORDING TO PETTENKOFER LIMIT 3000 ( HFW RQ DQ LQGLYLGXDO 2500 Reduced concentration, drowsi- ness, headache, etc. 2000 1500 Pettenkofer limit Disturbs 1000 Pettenkofer limit Pleasant Outdoor air Duration of the presence in the room in hours 8.1.5.
  • Page 32: Connection Of Remote Control Panel Or Modbus

    The app ‘MCB tool’ is for importing control board MCB settings from MCB to the media in a computer, and to export MCB settings from the media in a computer to MCB. Download the app from http://www.salda.lt/en/products/category/download_page/. 1. Choose connection type a.
  • Page 33 b. Modbus TCP/IP (connect with TCP/IP Modbus gateway (MB-GATEWAY)) Set IP of TCP/IP Modbus gateway (MB-GATEWAY) Press to connect 2. Connect to device (press “CONNECT” button) Device software version &RQ¿JXUDWLRQ UHDG VWDWXV &RQ¿JXUDWLRQ ZULWH VWDWXV Press to disconnect from device 3UHVV WR UHDG FRQ¿JXUDWLRQ IURP GHYLFH 3UHVV WR ZULWH FRQ¿JXUDWLRQ WR GHYLFH  5HDG FRQ¿JXUDWLRQ IURP GHYLFH DQG VDYH WR \RXU FRPSXWHU SUHVV ³5($' &21),* )520 %2$5'´...
  • Page 34: The Principal Connection Scheme Of Internal And External Components

     :ULWH FRQ¿JXUDWLRQ WR GHYLFH IURP \RXU FRPSXWHU SUHVV ³:5,7( &21),* 72 %2$5'´ EXWWRQ DQG VHOHFW FRQ¿JXUDWLRQ ¿OH 8.2. THE PRINCIPAL CONNECTION SCHEME OF INTERNAL AND EXTERNAL COMPONENTS )LJXUH   SP46 | EN SMARTY RV v2019.12...
  • Page 35 ;S *UHHQ\HOORZ       3OXJ 5* %OXH        &(( 0&% 9 %URZQ         & 3RZHU VXSSO\ 9  $  *UHHQ\HOORZ  %OXH  %URZQ -XPSHU SRVLWLRQV...
  • Page 36 ;  7DFKR 6XSSO\ IDQ VSHHG 530 ;  9LQ ;  7DFKR ([WUDFW IDQ VSHHG 530 ;  9LQ ;  *1' 6XSSO\ DLU IDQ 9 FRQWURO ;  $2 9'& ;  *1' ([WUDFW DLU IDQ 9 FRQWURO ;  $2 9'& ;  3( ;  *1' 5RWRU 530...
  • Page 37 56 '; FRROHU ;  9'& ;  67(3B% +HDWHU  SRZHU OLQH ;  + %URZQ %URZQ ;  /  ;  *1' ; 9 ;  $2 9'& ;  *1' ;  3( ;  *1' ;  9'&B23(1 5RWRU PRWRU ;  9'&B&/26( SRZHU VXSSO\...
  • Page 38 ;  $, 17& 7$  ([WUDFW DLU WHPSHUDWXUH VHQVRU ;  *1' ;  $, 17& 7-  6XSSO\ DLU WHPSHUDWXUH VHQVRU ;  *1' ;  $, 17& 7/  )UHVK DLU WHPSHUDWXWH VHQVRU ;  *1' ;  $, 17& 7(  ([KDXVW DLU WHPSHUDWXUH VHQVRU ;  *1' ;  $, 9'& ...
  • Page 39 .)('*.'3 .)('*.'3 .)('*.'3  ;  ;  ; )LJXUH   36N SMARTY RV v2019.12 EN |...
  • Page 40 .)('*.'3 .)('*.'3  )LJXUH   36N | EN SMARTY RV v2019.12...
  • Page 41 .)('*.'3 ; ; .)('*.13 .)('*.'3 )LJXUH   36N SMARTY RV v2019.12 EN |...
  • Page 42  *UHHQ\HOORZ  :KLWH  %ODFN &  %URZQ 5RWRU PRURW+$// VHQVRU & :KLWH 9 '& :KLWH :KLWH &20 )LJXUH   36N  %URZQ 9 '& 9 '&  %ODFN  %OXH &20 &20 )LJXUH   36N ;  %URZQ 57...
  • Page 43 .)('*.'3 .)('*.'3 .)('*.'3  ;  ;  ; )LJXUH   36N SMARTY RV v2019.12 EN |...
  • Page 44 ;  $, 17& 7$  ([WUDFW DLU WHPSHUDWXUH VHQVRU ;  *1' ;  $, 17& 7-  6XSSO\ DLU WHPSHUDWXUH VHQVRU ;  *1' ;  $, 17& 7/  )UHVK DLU WHPSHUDWXWH VHQVRU ;  *1' ;  $, 17& 7(  ([KDXVW DLU WHPSHUDWXUH VHQVRU ;  *1' ;  $, 9'& ...
  • Page 45 56 ;  9'& ;  67(3B% '; FRROHU ;  ;  + ;  / ;S  / ;  *1' ; 9 ;  $2 9'& ;  *1' +HDWHU SRZHU ;  3( VXSSO\ ;  *1' 5RWRU PRWRU ;  9'&B23(1 SRZHU VXSSO\...
  • Page 46 ;  7DFKR 6XSSO\ IDQ VSHHG 530 ;  9LQ ;  7DFKR ([WUDFW IDQ VSHHG 530 ;  9LQ ;  *1' 6XSSO\ DLU IDQ 9 FRQWURO ;  $2 9'& ;  *1' ([WUDFW DLU IDQ 9 FRQWURO ;  $2 9'& ;  3( ;  *1' 5RWRU 530...
  • Page 47 ;  ;  ;  ;  ;  ;  ; / &RRNHU KRRG ; 1 ; 3( ;  +HDWHU SRZHU ;  VXSSO\ 9 ;/ &DSDFLWRU ;  ;  5RWRU PRWRU ;  ;  ;  9'&...
  • Page 48: Electrical Connection Of The Units

    :KLWH 8OWUDVRQLF ZHOGLQJ *  :KLWH 0&% SRZHU 8OWUDVRQLF ZHOGLQJ *  VXSSO\  8OWUDVRQLF ZHOGLQJ * 3( :KLWH 8OWUDVRQLF ZHOGLQJ 9 ; ;   :KLWH 8OWUDVRQLF ZHOGLQJ 9 ;   :KLWH 3.& 5 $ +HDWHU :KLWH 8OWUDVRQLF ZHOGLQJ 5 $ 5RWRU PRWRU )LUH DODUP...
  • Page 49: Possible Faults And Troubleshooting

    • 8VH RQO\ SRZHU VRXUFH ZKLFK PHHWV WKH UHTXLUHPHQWV VSHFL¿HG RQ WKH GHYLFH ODEHO • 3RZHU VXSSO\ FDEOH VKRXOG EH VHOHFWHG EDVHG RQ WKH HOHFWULFDO VSHFL¿FDWLRQ RI WKH GHYLFH ,I WKH GHYLFH SRZHU VXSSO\ OLQH LV IDU IURP WKH XQLW the distance and voltage drop should be considered.
  • Page 50: Ecodesign Data Table

    AEC warm [ kWh ] AHS Average [ kWh/a ] 4192 4170 AHS Cold [ kWh/a ] 8201 8157 AHS Warm [ kWh/a ] 1896 1885 ErP Compliance 2018 2018 Internet address for disassembly instructions www.salda.lt | EN SMARTY RV v2019.12...
  • Page 51: Declaration Of Confomity

    Should any alterations be made in the products, this declaration will no longer apply. 1RWL¿HG ERG\ 9ã 7HFKQLNRV SULHåL URV WDUQ\ED 1DXJDUGXNR J  /7 ±  9LOQLXV /LWKXDQLD LGHQWL¿FDWLRQ QXPEHU  Quality: Salda UAB activities are in line with the international quality management system standard ISO 9001:2015. Date...
  • Page 52: Warranty

    3.4. when the unit was used not for its original purpose. 3.5. Company SALDA UAB is not responsible for potential loss of property or personal injury in cases where AHU is manufactured without a control system and the control system will be installed by the client or third parties. The manufacturer’s warranty does not cover devices that will be damaged by installing the control system.
  • Page 53 SMARTY RV v2019.12...
  • Page 54 SMARTY RV v2019.12...
  • Page 55 SMARTY RV v2019.12...
  • Page 56 Every 3-4 Filter replacement months** * - Look at the product label. ** - At least. NOTE. 7KH SXUFKDVHU LV UHTXLUHG WR ¿OO LQ WKH ³3URGXFW PDLQWHQDQFH WDEOH´ MAN000005 Ragainės g. 100 +370 41 540 415 Šiauliai LT-78109, LITHUANIA office@salda.lt...