CONCENTRATION ACCORDING TO PETTENKOFER LIMIT 8.1.6. CONECTION OF SUPPLY AND EXHAUST AIR DAMPERS 8.1.7. CONNECTION OF REMOTE CONTROL PANEL OR MODBUS 8.1.8. FIRE PLACE CONNECTION (SMARTY XV 1.1) 8.1.9. RECOMMENDED SCHEME FOR CONNECTION OF INTERNAL AND EXTERNAL COMPONENTS 9. POSSIBLE FAULTS AND TROUBLESHOOTING 10.
ODA - outdoor air; SUP - supply air; ETA - extract air; EHA - exhaust air. Figure. 2.3. Smarty 2 XV Technical label location and air duct Figure. 2.4. Smarty 3XV/4XV F2 Technical label location and air duct indication indication NOTE. Ducts are not the part of the unit. SMARTY XV v2020.3 EN |...
Salda Antifrost the air in from the room and the duct-exhaust gases out through chimney or extraction ducting. The heating appliance can be starved protection (see Salda Antifrost function in the Remote Controller Operation Manual). | EN SMARTY XV v2020.3...
Premium Smarty 4X V F2 1.2 Mini MCB Basic Advanced *- only pre-heater or heater Not suitable for operation in pools, saunas and other similar premises. 4.2. DIMENSIONS AND WEIGHT Figure 4.2.1. Smarty 2XV dimension SMARTY XV v2020.3 EN |...
4XV F2 Minimum outdoor air temperature Maximum outdoor air temperature Minimum extracted air temperature Maximum extracted air temperature Maximum extracted air relative humidity Minimum ambient air temperature Maximum ambient air temperature Installation indoor indoor indoor SMARTY XV v2020.3 EN |...
610 mm 610 mm 610 mm 610 mm Straight Fiting With O-ring F 1/2 M/M Rubber gasket d20xD28 s2mm 4.6. DESCRIPTION OF COMPONENTS Figure 4.6.1. Smarty 2XV Figure 4.6.2. Smarty 3XV/4XV F2 - By-Pass damper. | EN SMARTY XV v2020.3...
Accessories may be packed together with the product. Prior to transporting the unit, the accessories should be unpacked • Before commencing the installation of the unit, please check if all ordered equipment have been delivered. Any variation from the ordered equip- ment list must be reported to the product supplier. SMARTY XV v2020.3 EN |...
Figure 5.3.2. Smarty 3XV/4XV F2 5.4. PIPING AND INSTRUMENTATION DIAGRAM Figure 5.4.1. SMARTY XV miniMCB (* Available in 3XV/4XV F2 1.1 Figure 5.4.2. SMARTY XV miniMCB basic (* Only heater or models; ** Check the manual for details; *** Optional) preheater can be connected at a time;...
• Before connecting to the air duct system, the connection openings of ventilation unit should be closed. • • • • ment. • • • rying out maintenance, servicing and/or repairs signs may occur. Figure 5.5.1. Figure 5.5.2. Ceiling-mounting positions SMARTY XV v2020.3 EN |...
5.6. UNIT PLACING AND MOUNTING POSITIONING REQUIREMENTS 1,5xL Figure 5.6.1. 5.7. FLOOR MOUNTING Figure 5.7.1. 5.8. WALL-MOUNTING OF THE UNIT 30 mm Figure 5.8.1. mounting on the wall 5.9. DRAINAGE | EN SMARTY XV v2020.3...
• When installing air ducts next to the ventilation equipment, brackets must be used. They suppress vibration and assure secure installation of the • Air ducts are often mistakenly connected in inappropriate location. The ventilation units bear the labels indicating the correct air duct connection SMARTY XV v2020.3 EN |...
5.12.2. PRE-STARTUP RECOMENDATIONS OF THE UNIT (IN THE PRESENCE OF THE ENDUSER) • all electrical equipment protection components are properly connected (if they are additionally used), • earthling and protection systems are properly installed, • condition of all seals and sealing surfaces is proper. | EN SMARTY XV v2020.3...
Check the condensate discharge Condensate trap and discharge Clean assembly ter runs from the drip tray properly. 6.3. COVER OPENING Figure 6.3.1. Smarty 2XV Figure 6.3.2. Smarty 3XV/4XV F2 SMARTY XV v2020.3 EN |...
6.4. FILTERS MAINTENANCE • • Figure 6.4.1. Smarty 2XV Figure 6.4.2. Smarty 3XV/4XV F2 manual or on our website www.salda.lt 6.5. FAN MAINTENANCE • • The fan should be inspected and cleaned at least once per year. • • The fans features a heavy-duty ball bearing design. The motor is completely sealed and free of maintenance.
BYPASS DAMPERS AND PRE-HEATER MAINTENANCE • Bypass damper and pre-heater are mounted on one block. The pre-heater shall be disconnected by removing X29 connector. The bypass damp- er shall be disconnected by removing X25 . SMARTY XV v2020.3 EN |...
Figure 6.7.2. Smarty 3XV/4XV F2 6.8. CONTROL BOARD MAINTENANCE • • • Disconnect the connectors from the control board. • The connectors are marked according to connection location. Thus during automation reassembly please observe the marking of the connec- | EN SMARTY XV v2020.3...
SALDA AIR mobile application ST-SA-Control BMS over Modbus TCP/IP BMS over BACnet TCP/IP 7.2. DEVICE FUNCTIONS application and SALDA AIR mobile application. For unit control instructions, refer to the operation manual of the existing control device. SMARTY XV v2020.3 EN |...
2pcs.) 8.1. CONNECTION OF ACCESSORIES 8.1.1. HEATER AND PRE-HEATER 8.1.1.1. VERSION 1.1. Smarty XV 1.1. units feature one connection for external electrical air heater and one for external air pre-heater. Pre-heater is integrated inside the SMARTY XV v2020.3 EN |...
Page 22
EKA connection: EKA NIS connection: | EN SMARTY XV v2020.3...
Page 23
8.1.1.2. VERSION 1.2. Smarty XV 1.2. units feature one connection of external electrical heater/pre-heater. In factory settings, the connection is intended for the pre- EKA connection: SMARTY XV v2020.3 EN |...
Page 24
EKA NIS connection: | EN SMARTY XV v2020.3...
Page 25
For the Stouch control panel, changing of the settings is not possible • Service > Digital inputs > Heater protection inputs Set the manual and automatic protection modes of the heater or pre-heater (NC by default). SMARTY XV v2020.3 EN |...
Page 26
Installation based on air direction Air Damper M2 > Pre-Heater PE1 > Air Handling Unit. Heater Installation Diagram Mini MCB When using the supply air heater, the supply air sensor (TJ) must be installed downstream the heater (or cooler) at the length | EN SMARTY XV v2020.3...
/RH (input 0-10VDC) sensors. Sensors connection: Smarty 3XV 1.1 and Smarty 4XV F2 1.1 come with the integrated RH sensor connected. Smarty XV 1.2. units feature one connection for external CO /RH (input 0-10VDC) sensors. Sensors connection: There are 3 functions of these sensors: Supply RH, Extract RH and Extract CO Supply RH transmitter shall be installed inside supply air duct.
CONECTION OF SUPPLY AND EXHAUST AIR DAMPERS Installation diagram See PIPING AND INSTRUMENTATION DIAGRAM. Wiring diagram Automation controller D zone. Upon activation of output X13:3, the dampers open. Upon activation of output X13:4, the dampers close. | EN SMARTY XV v2020.3...
8.1.7. CONNECTION OF REMOTE CONTROL PANEL OR MODBUS Wiring diagram. Automation controller F zone, X18 connector. Switch Position Purpose 8.1.8. FIRE PLACE CONNECTION (SMARTY XV 1.1) Wiring diagram. Automation controller C zone, X23 connector. LED indication miniMCB miniEX1 LED1 LED1...
(if installed) Manual safety device is activated MUST be contacted to identify and eliminate the failure . Filter replacement needed on the remote control panel broken, or its pressure is set improperly. SMARTY XV v2020.3 EN |...
EN IEC 61000-6-1:2019-03 - Electromagnetic compatibility (EMC) -- Part 6-1: Generic standards - Immunity for residential, commercial and light-industrial environments. LST EN 61000-6-3:2008 - Electromagnetic compatibility (EMC) -- Part 6-3: Generic standards - Emission standard for residential, commercial and light-industrial environments. Quality: ISO 9001:2015. Date 2020-10-23 Giedrius Taujenis Director product development | EN SMARTY XV v2020.3...
In order to avoid any misunderstandings, please read the instructions for installation and operation of the product as well as delete, or rewrite The manufacturer reserves the right to refuse provision of free warranty servicing in cases when the warranty conditions listed below are disregarded. SMARTY XV v2020.3 EN |...
Page 48
Once per year** Every 3-4 Filter replacement months** Look at the product label. ** - At least. NOTE. The customer shall be required to complete the Product Maintenance Table. MANUALS IN OTHER LANGUAGES https://select.salda.lt/file/ https://select.salda.lt/file/ https://select.salda.lt/file/ https://select.salda.lt/file/ https://select.salda.lt/file/ smartyxvde smartyxvdk smartyxvfr smartyxvlt smartyxvnl https://select.salda.lt/file/...
Need help?
Do you have a question about the SMARTY XV and is the answer not in the manual?