SMARTY XP S300
EN
MOUNTING AND INSTALLATION INSTRUCTION

Advertisement

Table of Contents
loading

Summary of Contents for Salda SMARTY XP S300

  • Page 1 SMARTY XP S300 MOUNTING AND INSTALLATION INSTRUCTION...
  • Page 2: Table Of Contents

    10.5. FIREPLACE PROTECTION, SYSTEM MODE SWITCH OR RAPID VENTILATION SWITCH INPUT 10.6. ALARM INDICATION OUTPUT 10.7. REMOTE CONTROLLER AND KNX ROOM SENSORS 11. OPERATING THE UNIT 12. ELECTRICAL WIRING DIAGRAMS 13. POSSIBLE FAULTS AND TROUBLESHOOTING 14. ECODESIGN DATA TABLE | EN SMARTY XP S300 v2022.1...
  • Page 3 15. DECLARATION OF CONFIMITY 16. WARRANTY 16.1. LIMITED WARRANTY COUPON SMARTY XP S300 v2022.1 EN |...
  • Page 4: Symbols And Marking

    ODA - outdoor air; SUP - supply air; ETA - extract air; EHA - exhaust air. Figure. 2.3. Smarty 2XP S300 Technical label location and air duct indication Figure. 2.4. Smarty 3-4XP S300 Technical label location and air duct indication NOTE. Ducts are not the part of the unit. | EN SMARTY XP S300 v2022.1...
  • Page 5: Safety Instructions And Precautions

    Salda Antifrost the air in from the room and the duct-exhaust gases out through chimney or extraction ducting. The heating appliance can be starved protection (see Salda Antifrost function in the Remote Controller Operation Manual). SMARTY XP S300 v2022.1 EN |...
  • Page 6: Information About The Product

    Smarty 3X P S300 S300 Advanced Smarty 4X P S300 S300 Advanced *- only pre-heater or heater Not suitable for operation in pools, saunas and other similar premises. 4.2. DIMENSIONS AND WEIGHT Figure 4.2.1. Smarty 2XP S300 | EN SMARTY XP S300 v2022.1...
  • Page 7 [mm] [mm] [mm] øD [mm] øDa [mm] [mm] G1/2 G1/2 G1/2 G3/8 G3/8 G3/8 [mm] [mm] 1047 1268 1268 [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] Weight [kg] SMARTY XP S300 v2022.1 EN |...
  • Page 8: Technical Data

    (class, dimensions LxWxH) Device protection class IP 34 IP 34 IP-34 According to EN 13141-7. Acoustic data: check the product page on https://select.salda.lt Not suitable for installation in living rooms: additional noise insulation required. 4.4. OPERATING CONDITIONS SMARTY 2X P...
  • Page 9: Description Of Components

    DESCRIPTION OF COMPONENTS Figure 4.6.1. Smarty 2 XP S300 construction Figure 4.6.2. Smarty 3-4XP S300 construction 1 - Plate heat exchanger; 2 - Supply fan; 3 - Exhaust fan; 4 - By-pass damper (panel). SMARTY XP S300 v2022.1 EN |...
  • Page 10: Instalation

    1400 2175 1450 Smarty 4X P 1400 2175 1450 Figure 5.2.1. Lifting by forklift. In order to prevent damage to the casing, only a product placed on a pallet should be lifted. 5.3. UNPACKING | EN SMARTY XP S300 v2022.1...
  • Page 11: Piping And Instrumentation Diagram

    5.4. PIPING AND INSTRUMENTATION DIAGRAM Figure 5.4.1. SMARTY XP S300 (* Only heater or preheater can be connected at a time; ** Components connection only with PE1; *** Components connection only without PE1) THE LIST OF COMPONENTS...
  • Page 12: Unit Placing And Mounting Positioning Requirements

    α Figure 5.5.1. 5.6. UNIT PLACING AND MOUNTING POSITIONING REQUIREMENTS 1,5xL Figure 5.6.1. 5.7. CEILING-MOUNTING OF THE UNIT Ceiling-mounting of the unit ⌀ Drainage system installation (øD=150 mm) | EN SMARTY XP S300 v2022.1...
  • Page 13: Connection Of The Air Duct

    The manufacturer does not assume any liability for personal injuries and property damage due to nonconformance with the provided instructions. 5.10. START-UP RECOMMENDATIONS 5.10.1. SYSTEM PROTECTION 2XP S300 3XP S300 4XP S300 SMARTY Mains Fuse SMARTY XP S300 v2022.1 EN |...
  • Page 14: Pre-Startup Recomendations Of The Unit (In The Presence Of The Enduser)

    5.10.2. • all electrical equipment protection components are properly connected (if they are additionally used), • earthling and protection systems are properly installed, • condition of all seals and sealing surfaces is proper. | EN SMARTY XP S300 v2022.1...
  • Page 15: Maintenance

    All the contactors in the product or in its accessories must be checked. Check the condensate discharge Condensate trap and discharge Clean assembly ter runs from the drip tray properly. 6.3. COVER OPENING Smarty 2X P S300 SMARTY XP S300 v2022.1 EN |...
  • Page 16: Filters Maintenance

    6.4. FILTERS MAINTENANCE • • 6.5. HEAT EXCHANGER MAINTENANCE • Proceed to maintenance and repair every time the fan rotation is stopped. Clean the heat exchanger once per year. • Smarty 2X P S300 | EN SMARTY XP S300 v2022.1...
  • Page 17: Fan Maintenance

    Prior to commencing any maintenance or repairs , make sure the ventilation units is disconnected from the power source. Smarty XP units: • • from. Figure 6.6.1. Smarty XP S300 fans Smarty 2X P S300 SMARTY XP S300 v2022.1 EN |...
  • Page 18: Bypass Dampers Maintenance

    • Reconnect X4 connector to the control board. 6.8. CONTROL BOARD MAINTENANCE • • • Remove the control board through the front part of the device. • and connector to corresponding connection terminal and connector. | EN SMARTY XP S300 v2022.1...
  • Page 19 Smarty 2X P S300 Smarty 3-4XP S300 SMARTY XP S300 v2022.1 EN |...
  • Page 20: Control

    Modbus RTU (485) WIFI stick + mobile app POS8.4440 BACnet IP 7.2. DEVICE FUNCTIONS environment settings. application for installer and service users. For unit control instructions, refer to the operation manual of the existing control device. | EN SMARTY XP S300 v2022.1...
  • Page 21: Connection Of Accessories

    ELECTRIC HEATER > SUPPLY AIR SENSOR (TJ). Mini MCB Siemens S300 8.1.2. PREHEATER 1. Electric preheating coil command; 2. Air temperature after preheating coil; 3. Preheating coil overtemperature detector; 4. Preheating coil position signal. SMARTY XP S300 v2022.1 EN |...
  • Page 22: Outside Air Dampers

    OUTSIDE AIR DAMPERS of output Q34 (T14:1), dampers shall open. Upon deactivation of output, dampers shall close. When activated, 230V voltage is applied to Q34 Figure 8.2.1. Connection for outside dampers WARNING: High voltage on output. | EN SMARTY XP S300 v2022.1...
  • Page 23: Smoke Detector

    Figure 8.4.1. D2 digital input connection ACCESSORIES SETUP. 8.5. OPERATION INDICATION OUTPUT If indication about the status of the air handling unit is needed, it can be connected to dedicated Q24 signal on T7:1. When AHU is ON, indication SMARTY XP S300 v2022.1 EN |...
  • Page 24: Alarm Indication Output

    Air Handling unit can be connected to the Building Management System via BACnet IP or Modbus (RS485). BACnet Vendor Name: Siemens Building Technologies Default BACnet/IP port: 47808 (0xBAC0) Default Device Object Instance number: 1 Baudrate: 19200 bps Data: 8 Bit Parity: Even Stop bit: 1 Slave address: 1 | EN SMARTY XP S300 v2022.1...
  • Page 25: Room Co Transmitter Installation Recommendation

    . min. 60 cm max. 400m If the duct CO transmitter is used, it must be installed in the extract air duct. To install duct transmitters, hole drilling tools are required . SMARTY XP S300 v2022.1 EN |...
  • Page 26: Concentration According To Pettenkofer Limit

    8.9. CONCENTRATION ACCORDING TO PETTENKOFER LIMIT | EN SMARTY XP S300 v2022.1...
  • Page 27 9. PINOUT OF THE CONTROLLER Figure. 9.1. S300 controller SMARTY XP S300 v2022.1 EN |...
  • Page 28: Accessories Setup

    SIBPAdmin). • Start ABT Go application and open menu. • Log in to access the device (by default: user name is Administrator OneBT • Go to CONFIGURATION ONLINE CONFIGURATION BASIC and ONLINE CONFIGURATION EXTENDED. | EN SMARTY XP S300 v2022.1...
  • Page 29: Heater

    3. INPUT ROOM OPERATING MODE UNOCCUPIED; 4. INPUT ROOM OPERATING MODE PROTECTION. • In CONFIGURATION ONLINE CONFIGURATION EXTENDED and press OK • Select D2 as RAPID VENTILATION INPUT. After D2 APPLY – RESTART DEVICE activation press DONE. SMARTY XP S300 v2022.1 EN |...
  • Page 30: Alarm Indication Output

    • Set SELECTION FOR ROOM SENSOR QMX3.P30 as ACTIVE. • Set SELECTION FOR ROOM SENSOR QMX3.P40 as ACTIVE. • Set SELECTION FOR ROOM SENSOR QMX3.P70 as ACTIVE. • Press APPLY – RESTART DEVICE DONE. | EN SMARTY XP S300 v2022.1...
  • Page 31: Operating The Unit

    MANUAL control mode: • Comfort • Economy • Unoccupied • Protection APPLICATION FUNCTIONALITIES. Folow the link on the last page of this document. PRE-STARTUP RECOMMENDA- TIONS OF THE UNIT (IN PRESENCE OF THE ENDUSER). SMARTY XP S300 v2022.1 EN |...
  • Page 32: Electrical Wiring Diagrams

    12. ELECTRICAL WIRING DIAGRAMS Figure. 12.1. Smarty power supply and fans | EN SMARTY XP S300 v2022.1...
  • Page 33 Figure. 12.2. Smarty temperature sensors and bypass SMARTY XP S300 v2022.1 EN |...
  • Page 34: Possible Faults And Troubleshooting

    (if installed) Manual safety device is activated MUST be contacted to identify and eliminate the failure . Filter replacement needed on the remote control panel broken, or its pressure is set improperly. | EN SMARTY XP S300 v2022.1...
  • Page 35: Ecodesign Data Table

    [ dB(A) ] /s ] 0,077 [ Pa ] [ W/(m /h) ] 0,28 Declared maximum internal leakage rates Declared maximum external leakage rates Timer ErP Compliance 2018 Internet address for disassembly instructions https://select.salda.lt SMARTY XP S300 v2022.1 EN |...
  • Page 36 [ dB(A) ] /s ] 0,11 [ Pa ] [ W/(m /h) ] 0,37 Declared maximum internal leakage rates Declared maximum external leakage rates Timer ErP Compliance 2018 Internet address for disassembly instructions https://select.salda.lt | EN SMARTY XP S300 v2022.1...
  • Page 37 EN IEC 61000-6-1:2019-03 - Electromagnetic compatibility (EMC) -- Part 6-1: Generic standards - Immunity for residential, commercial and light-industrial environments. LST EN 61000-6-3:2008 - Electromagnetic compatibility (EMC) -- Part 6-3: Generic standards - Emission standard for residential, commercial and light-industrial environments. Quality: ISO 9001:2015. Date 2020-10-23 Giedrius Taujenis Director product development SMARTY XP S300 v2022.1 EN |...
  • Page 38 The Limited Warranty Coupon shall be valid provided that the seller’s stamps and records are clear. It is not allowed to change, delete, or rewrite The manufacturer reserves the right to refuse provision of free warranty servicing in cases when the warranty conditions listed below are disregarded. | EN SMARTY XP S300 v2022.1...
  • Page 39 SMARTY XP S300 v2022,1...
  • Page 40 Filter replacement months** Look at the product label. ** - At least. NOTE. The customer shall be required to complete the Product Maintenance Table. LINKS TO OTHER DOCUMENTS AHU’S CONTROLLER (S300) ROOM OPERATOR UNIT POS8 LT MANUAL https://select.salda.lt/file/ smartyxps300lt s8en MAN000377...