Advertisement

SMARTY XV
EN
MOUNTING AND INSTALLATION INSTRUCTION

Advertisement

Table of Contents
loading

Summary of Contents for Salda Smarty 2XV 1.1

  • Page 1 SMARTY XV MOUNTING AND INSTALLATION INSTRUCTION...
  • Page 2: Table Of Contents

    1. CONTENT 2. SYMBOLS AND MARKING 3. SAFETY INSTRUCTIONS AND PRECAUTIONS 4. INFORMATION ABOUT THE PRODUCT 4.1. DESCRIPTION 4.2. DIMENSIONS AND WEIGHT 4.3. TECHNICAL DATA 4.4. OPERATING CONDITIONS 4.5. STANDART PACKAGE OF COMPONENTS 4.6. DESCRIPTION OF COMPONENTS 5. INSTALATION 5.1. RECEPTION OF GOODS 5.2.
  • Page 3: Symbols And Marking

    2. SYMBOLS AND MARKING Warning – pay attention Additional information Apply the auxiliary label on the unit (on an easily accessible location) or on the dashed location of the technical manual in order to keep the im- portant information about the unit. Figure.
  • Page 4: Safety Instructions And Precautions

    In exceptional cases, harmful gases could be drawn out of the chimney or extraction ducting back into the room. In such case we strictly recommend to turn off Salda Antifrost and use an external preheater for heat exchanger anti-frost protection (see Salda Antifrost function in the Remote Controller Operation Manual).
  • Page 5: Information About The Product

    4. INFORMATION ABOUT THE PRODUCT 4.1. DESCRIPTION Smarty XV is the residential air handling unit with a high efficiency (up to 90%) counter flow heat exchanger. The unit supplies ventilation in home and takes the heat from exhaust air. AHU complies with ErP 2018 and Passivhaus requirements. The unit is operated by a separate remote control panel or though separate MB-Gateway by PC.
  • Page 6 Figure 4.2.2. Smarty 3XV, Smarty 4XV F2 dimension 2XV 1.1 2XV 1.2 3XV 1.1 3XV 1.2 4XV F2 1.1 4XV F2 1.2 SMARTY [mm] [mm] [mm] øD [mm] øDa [mm] [mm] ød G3/8 G3/8 G1/2 G1/2 G1/2 G1/2 [mm] [mm] [mm] [mm] [mm]...
  • Page 7: Technical Data

    IP 34 IP 34 IP 34 IP 34 IP 34 According to EN 13141-7. Acoustic data: check the product page on www.salda.lt Not suitable for installation in living rooms: additional noise insulation required. 4.4. OPERATING CONDITIONS SMARTY 4XV F2 Minimum outdoor air temperature...
  • Page 8: Standart Package Of Components

    4.5. STANDART PACKAGE OF COMPONENTS SMARTY 2XV 1.1 2XV 1.2 3XV 1.1 3XV 1.2 4XV F2 1.1 4XV F2 1.2 Bush caps BFG15 Key M4 Z-type Outlet pipe G3/8 Siphon D25 202.085 Bracket 2281027 Fix - PV gasket 6x20 (white) 605 mm 605 mm 1300 mm...
  • Page 9: Instalation

    5. INSTALATION 5.1. RECEPTION OF GOODS Each device is carefully checked before transportation. When receiving the goods, checking the devices for any damage made during transporta- tion is recommended. If any damage to the unit is observed, immediately contact the representatives of a transport company. Please inform the representative of the manufacturer, if any deviation of the device is noticed.
  • Page 10: Piping And Instrumentation Diagram

    Figure 5.3.1. Smarty 2XV Figure 5.3.2. Smarty 3XV/4XV F2 5.4. PIPING AND INSTRUMENTATION DIAGRAM Figure 5.4.1. SMARTY XV miniMCB (* Available in 3XV/4XV F2 1.1 Figure 5.4.2. SMARTY XV miniMCB basic (* Only heater or models; ** Check the manual for details; *** Optional) preheater can be connected at a time;...
  • Page 11: Mounting

    THE LIST OF COMPONENTS Plate heat exchanger Supply air fan α Extract air filter Supply air filter Exhaust fan Extract air temperature sensor Exhaust air temperature sensor Supply air temperature sensor Extract air temperature and humidity sensor sensor* RH sensor* Computer Electric heater Electric pre-heater...
  • Page 12: Unit Placing And Mounting Positioning Requirements

    5.6. UNIT PLACING AND MOUNTING POSITIONING REQUIREMENTS 1,5xL 1,5xL Figure 5.6.1. Min. distance to open the door - 1,5xL; Min. distance to open the control box door - H > 400 mm. 5.7. FLOOR MOUNTING Figure 5.7.1. floor mounting (optional accessory required) 5.8.
  • Page 13: Connection Of The Air Duct

    DRAINAGE SYSTEM INSTALLATION SMARTY 2XV øD Figure 5.9.1. Drainage system installation (øD=150 mm) It’s required to connect condensate drainage system after hanging or placing of air handling unit. Insert condensate draining into AHU. Condensate draining must be lubricated with a sealant (I-VII) and connected to a condensate removal system. Remove the sticker on the bottom of the unit, which covers a drainage hole.
  • Page 14: Connection Of The Unit To Electric Network

    For flange diameters see chapter " DIMENSIONS AND WEIGHT". Right side connection Left side connection 5.11. CONNECTION OF THE UNIT TO ELECTRIC NETWORK • Supply voltage to the unit must be connected by a qualified specialist following the manufacturer’s instructions and applicable safety guidelines. •...
  • Page 15: Maintenance

    6. MAINTENANCE 6.1. SAFETY INSTRUCTIONS Unplug the unit from the mains before opening the door (disconnect the power plug from the outlet or in case a two-pole au- tomatic circuit breaker installed, disconnect it as well. Make sure that it cannot be turned on by third parties) and wait until the fans completely stop (for about 2 min.).
  • Page 16: Filters Maintenance

    Figure 6.4.2. Smarty 3XV/4XV F2 After changing the filters, please reload the filter timer. The instruction on reloading can be found in the control panel opera- tion manual or on our website www.salda.lt Operation of the unit without filters is not allowed.
  • Page 17: Heat Exchanger Maintenance

    Figure 6.5.1. Smarty 2XV/3XV Figure 6.5.2. Smarty 4XV F2 Figure 6.5.3. Smarty 2XV Figure 6.5.4. Smarty 3XV/4XV F2 6.6. HEAT EXCHANGER MAINTENANCE • Proceed to maintenance and repair after any rotation in the fan stopped. • Clean the heat exchanger once a year. •...
  • Page 18: Control Board Maintenance

    Figure 6.7.1. Smarty 2XV Figure 6.7.2. Smarty 3XV/4XV F2 6.8. CONTROL BOARD MAINTENANCE • Unscrew the front bolt securing the control board holder to the unit casing. • Withdraw the automation through the front part. • Disconnect the connectors from the control board. •...
  • Page 19: Control

    1. Selected control interface (remote control panel, MB-GATEWAY, etc.). The selected interface affects access to the information and settings, however, it does not affect the logic of control. Full access to the information and settings is available on ST-SA-Control, MB-GATEWAY WEB application and SALDA AIR mobile application. 2. Unit configuration (internal/external components, sensors and control board settings).
  • Page 20: Accessories

    8. ACCESSORIES SMARTY 2XV 1.1 2XV 1.2 3XV 1.1 3XV 1.2 4XV F2 1.1 4XV F2 1.2 Legs Smarty Legs ACC000009 ACC000009 ACC000009 ACC000009 ACC000009 ACC000009 2XV/3XV/4XV WSG 160 FIT000403 FIT000403 FIT000403 FIT000403 Outlet covers ALU 125 FIT000126 FIT000126 ALU 160 FIT000127 FIT000127 FIT000127...
  • Page 21: Connection Of Accessories

    MUTE 125X600 FIT000287 FIT000287 MUTE 125X900 FIT000288 FIT000288 Silencers MUTE 160X600 FIT000289 FIT000289 FIT000289 FIT000289 MUTE 160X900 FIT000290 FIT000290 FIT000290 FIT000290 EKA 125-0.3-1 f ACC003721 ACC003721 EKA 125-0,6-1 f ACC000329 ACC000329 EKA 125-0,9-1 f ACC000330 ACC000330 EKA 125-1,2-1f ACC003722 ACC003722 EKA 125-1,5-1 f ACC000331 ACC000331...
  • Page 22 EKA connection: EKA NIS connection: Automatic and manual protection must be connected to EX1 controller ‘s X23 connector when an electric heater is equipped with these connection terminals. Otherwise, jumpers are installed on the X23 connect or protection inputs. | EN SMARTY XV v2020.3...
  • Page 23 8.1.1.2. VERSION 1.2. Smarty XV 1.2. units feature one connection of external electrical heater/pre-heater. In factory settings, the connection is intended for the pre- heater, however, it can be configured for the heater. Heater/pre-heater can be controlled by the following signals: •...
  • Page 24 EKA NIS connection: | EN SMARTY XV v2020.3...
  • Page 25 Automatic and manual protection must be connected to the controller’s X5 connector when an electric heater/pre-heater is equipped with these connection terminals. Otherwise, jumpers are installed on the X5 connector protection inputs. Since the pre-heater must be connected according to the factory settings, the settings should be changed in the environment of the MB-Gateway WEB application service or on the ST-SA-Control panel.
  • Page 26 • Service > Heaters > Supply air heater or outdoor air pre-heater Set either a heater or pre-heater and the type of the heater or pre-heater as well as the steps to be performed in case of protection signal activation. Settings with the ST-SA-Control panel 1.
  • Page 27: Fire Protection Signal Input (Fire Protection Input (Nc))

    8.1.2. FIRE PROTECTION SIGNAL INPUT (FIRE PROTECTION INPUT (NC)) Fire protection signal input must be normally closed, until the fire protection system is not connected a jumper is installed in the factory. Automation controller A zone X4 More information can be found in the MCB miniMCB Technical Manual. 8.1.3.
  • Page 28: Room Co Transmitter Installation Recommendation

    8.1.4. ROOM CO TRANSMITTER INSTALLATION RECOMMENDATION 5 0 c m i n . min. 60 cm max. 400m If the duct CO transmitter is used, it must be installed in the extract air duct. To install duct transmitters, hole drilling tools are required .
  • Page 29: Connection Of Remote Control Panel Or Modbus

    8.1.7. CONNECTION OF REMOTE CONTROL PANEL OR MODBUS Wiring diagram. Automation controller F zone, X18 connector. Switch position for X18 connector configuration Switch Position Purpose 120R line termination resistor (On/Off) 8.1.8. FIRE PLACE CONNECTION (SMARTY XV 1.1) Wiring diagram. Automation controller C zone, X23 connector. LED indication miniMCB miniEX1...
  • Page 30: Recommended Scheme For Connection Of Internal And External Components

    8.1.9. RECOMMENDED SCHEME FOR CONNECTION OF INTERNAL AND EXTERNAL COMPONENTS *Only Smarty 1.1 versions have N2 module. Figure 8.1.9.1. Smarty 2XV 1.1, Smarty 2XV/3XV/4XV F2 1.2 (219.1017.0.1.1-PS) | EN SMARTY XV v2020.3...
  • Page 31 Figure 8.1.9.2. Smarty 2XV 1.1, Smarty 2XV/3XV/4XV F2 1.2 (219.1017.0.1.2-PS) SMARTY XV v2020.3 EN |...
  • Page 32 Figure 8.1.9.3. Smarty 2XV 1.1, Smarty 2XV/3XV/4XV F2 1.2 (219.1017.0.1.3-PS) | EN SMARTY XV v2020.3...
  • Page 33 Figure 8.1.9.4. Bypass (SMARTY ZP3XV-0k) Figure 8.1.9.5. Preheater, Bypass wiring (Smarty 3XV-PE-0k) SMARTY XV v2020.3 EN |...
  • Page 34 BU - Blue - Mėlynas RD - Red - Raudonas GN/YE - Green/Yellow - Žalias/Ge DUTIES / NAME SIGNATURE DATE SP42 EI D. Aleksandravičius UAB"SALDA" 2016-03-22 DRAWN BY ns (MiniMCB) EI A. Šklenikas 2016-03-22 CHECKED BY Principle connection scheme 2016-03-22 CHECKED BY Figure 8.1.9.7.
  • Page 35 Figure 8.1.9.8. External preheater (SP45) SMARTY XV v2020.3 EN |...
  • Page 36 Figure 8.1.9.9. Smarty 3XV/4XV F2 1.1 (219.1349.0.1.1-PS) | EN SMARTY XV v2020.3...
  • Page 37 Figure 8.1.9.10. Smarty 3XV/4XV F2 1.1 (219.1349.0.1.2-PS) SMARTY XV v2020.3 EN |...
  • Page 38 Figure 8.1.9.11. Smarty 3XV/4XV F2 1.1 (219.1349.0.1.3-PS) | EN SMARTY XV v2020.3...
  • Page 39: Possible Faults And Troubleshooting

    9. POSSIBLE FAULTS AND TROUBLESHOOTING FAILURE CAUSE EXPLANATION / CORRECTIVE ACTIONS Check whether the device is connected to the No supply voltage power network Switch on only if the unit condition has been Unit is not operating Protection device is off or the current evaluated by a qualified electrician.
  • Page 40: Ecodesign Data Table

    10. ECODESIGN DATA TABLE MODEL SMARTY 2XV 1.1 Specific energy consumption SEC Class Climate Control Control typology (SEC) zone factor [ kWh/m²/a ] [ kWh/a ] [ kWh/a ] Clock control (standard) 0,95 -36,9 4610 Average Central demand control (opt. with 1 sensor)
  • Page 41 [ % ] Declared maximum external leakage rates [ % ] Possition and description of visual filter warning for RVU’s Timer ErP Compliance 2018 Internet address for disassembly instructions www.salda.lt MODEL SMARTY 3XV 1.1 Specific energy consumption SEC Class Climate Control...
  • Page 42 [ % ] Declared maximum external leakage rates [ % ] Possition and description of visual filter warning for RVU’s Timer ErP Compliance 2018 Internet address for disassembly instructions www.salda.lt MODEL SMARTY 4XV F2 1.1 Specific energy consumption SEC Class Climate Control...
  • Page 43 Declared maximum internal leakage rates [ % ] Declared maximum external leakage rates [ % ] Possition and description of visual filter warning for RVU’s Timer ErP Compliance 2018 Internet address for disassembly instructions www.salda.lt SMARTY XV v2020.3 EN |...
  • Page 44: Declaration Of Confimity

    LST EN 61000-6-3:2007 - Electromagnetic compatibility (EMC) -- Part 6-3: Generic standards - Emission standard for residential, commercial and light-industrial environments. Should any alterations be made in the products, this declaration will no longer apply. Quality: SALDA UAB activities are in line with the international quality management system standard ISO 9001:2015. Date 2020-03-23...
  • Page 45: Warranty

    3.4. when the unit was used not for its original purpose. 3.5. Company SALDA UAB is not responsible for potential loss of property or personal injury in cases where AHU is manufactured without a con- trol system and the control system will be installed by the client or third parties. The manufacturer’s warranty does not cover devices that will be damaged by installing the control system.
  • Page 46 SMARTY XV v2020.3...
  • Page 47 SMARTY XV v2020.3...
  • Page 48 Once per year** Every 3-4 Filter replacement months** Look at the product label. ** - At least. NOTE. The customer shall be required to complete the Product Maintenance Table. MAN000306 MAN000306 Ragainės g. 100 +370 41 540 415 Šiauliai LT-78109, LITHUANIA office@salda.lt...

Table of Contents