Specifications
Environmental Specifications
Operating Temperature
Humidity
Enclosure
Weight
Power Supply Requirements (DC)
Power Supply Source
Power Supply Voltage
Power Supply Power
Power Supply Cable
Power Supply Requirements (AC)
Power Supply Source
Power Supply Voltage
Power Supply Power
Power Supply Cable
12/24 V, 10 A Analog Battery Charger
Nominal Input AC Line Voltage
Operating AC Line Voltage
Range
Input AC Line Frequency
AC Line Fuse
Battery Fuse
Nominal Charge Rate
Equalize Voltage (typ.)
Float Voltage (typ.)
Current at Equalize to Float Tran-
sition (typ.)
Battery Under Voltage Shutdown
(typ.)
LED Indicators
AC Line Voltage > 108 V
Battery Connected and
Charging
NOTE: The Green LED must be ON to obtain a valid battery charging indication. Yellow LED is ON if charge
current > approximately 2 amps.
Battery Current Drain (AC Power
OFF)
AC Line Connections
Battery Connections
Control Connections
NOTE: Normally Open (N.O.) Contact closes when AC line voltage is applied. N.O. Contact opens when AC line
voltage is removed.
Owner's Manual for Power Zone Pro Sync
-40 °F (-40 °C) to 140 °F (60 °C)
0% to 95% Non-Condensing
UL Type 1
62 lbs (if all components are installed)
Battery
6 V
to 35 V
(12/24 V
31 Watts maximum
2 wires - voltage drop across each conductor must be less than 1 V
Emergency Power (utility)
120/240 V
700 Watts maximum
2 wires - voltage drop across each conductor must be less than 1 V
120 V
108 V
to 132 V
50 or 60 Hz
®
5 Amp, 5x20 mm, Littelfuse
15 A, Littelfuse ATO Blade (part no. 257015)
10 A
13.8/27.6 V
13.0/26.0 V
5 A
11/22 V
Green LED ON
Yellow LED ON
30 mA (typical)
via terminal block (AC Hot, AC Neut, and GND)
via terminal block (Pos (+), Neg (-))
AC Power Fail Relay, Form C, 2 A, 12/24 V
Nominal)
(part no. 218005)
General Information
7
Need help?
Do you have a question about the Power Zone Pro Sync and is the answer not in the manual?
Questions and answers