Specifications - Generac Power Systems Deep Sea Electronics G8601 Owner's Manual

Table of Contents

Advertisement

General Information

Specifications

Supply
Minimum Supply Voltage
Cranking Dropouts
Maximum Supply Voltage
Reverse Polarity Protection
Maximum Operating Current
Maximum Standby Current
Maximum Current When In Sleep Mode
Typical Power
(Controller On, Heater Off)
Typical Power
(Controller On, Heater On)
Generator and Bus
Voltage Range
Frequency Range
Current Range
Magnetic Pickup
Voltage Range
Frequency Range
Inputs
Digital Inputs
Analog Inputs
Outputs Current Limit
Output A & B (Fuel & Start)
Output C & D
Auxiliary Outputs E to L
Temperature
Storage Temperature Range
Operating Temperature w/o display heater
Operating Temperature w/ display heater
8
5 VDC continuous
Able to survive 0 VDC for 100 ms, provided supply was at least
15 VDC for 2 seconds before the dropout and recovers to 5
VDC afterwards.
35 VDC continuous (60 VDC protection)
-35 VDC continuous
700 mA at 12 VDC
350 mA at 24 VDC
350 mA at 12VDC
190 mA at 24 VDC
110 mA at 12 VDC
60 mA at 24 VDC
4.0 W to 4.5 W
4.5 W to 11 W
25 V to 720 VAC (Phase to Phase)
3.5 Hz to 75 Hz
5 A Maximum Continuous Current
+/- 0.5 VDC to 70 VDC RMS
5 Hz to 10,000 Hz RMS
16 Configurable Inputs
7 Configurable Inputs
15 A DC supplied from E-Stop (total A+B Max 15 A)
8 A Resistive at 250 V AC
2 A Resistive at supply voltage
-40 °C to +85 °C / -40 °F to +185 °F
-30 °C to +70 °C/ -22 °F to +158 °F
-40 °C to +70 °C / -40 °F to +158 °F
Deep Sea Electronics® G8601 Controller Owner's Manual

Advertisement

Table of Contents
loading

Table of Contents