Generac Power Systems Power Zone Pro Sync Owner's Manual page 36

Table of Contents

Advertisement

Troubleshooting
Alarm Display Text
CAN GOV1 MODULE ERROR
CAN AVR1 MODULE ERROR
CAN BAT1 MODULE ERROR
CAN UNKNOWN MODULE ERROR
CAN GOV1 MODULE WARNING
CAN AVR1 MODULE WARNING
CAN BAT1 MODULE WARNING
CAN UNKNOWN MODULE WARNING
CAN GOV1 ACK ERROR
CAN AVR1 ACK ERROR
CAN BAT1 ACK ERROR
CAN UNKNOWN ACK ERROR
ETH BAD MAC
ETH BAD SWITCH
ETH OTHER ERROR
LOST DISPLAY
SPI2 ERROR
MCU CORE VERSION ERROR
STACK OVERFLOW ERROR
KEYSWITCH NOT SETUP
REMOTE START 1 NOT SETUP
MCB STATUS 1 NOT SETUP
32
Type
Alarm Description
SD
Power Zone CAN bus Governor produced an
error. Can be numbered 1-4.
SD
Power Zone CAN bus AVR produced an error.
Can be numbered 1-4.
AL
Power Zone CAN bus Battery Charger produced
an error. Can be numbered 1-4.
SD
An unknown Power Zone CAN bus module
produced an error
WN
Power Zone CAN bus Governor produced a
warning. Can be numbered 1-4.
WN
Power Zone CAN bus AVR produced a warning.
Can be numbered 1-4.
WN
Power Zone CAN bus Battery Charger produced
a warning. Can be numbered 1-4.
WN
An unknown Power Zone CAN bus module
produced a warning
WN
Power Zone CAN bus Governor acknowledged
an error. Can be numbered 1-4.
WN
Power Zone CAN bus AVR acknowledged an
error. Can be numbered 1-4.
WN
Power Zone CAN bus Battery Charger
acknowledged an error. Can be numbered 1-4.
WN
An unknown Power Zone CAN bus module
acknowledged an error
WN
Read invalid MAC address from internal
EEPROM
WN
Internal Ethernet Switch has failed
WN
An Ethernet error has occurred
WN
Power Zone Display has been lost or is
unresponsive
WN
Communication fault with NV memory
SD
A/D Processor program missing
SD
Microcontroller operating system stack overflow
detected
SD
See
AI, AO, DI and DO XXX NOT SETUP
Alarms.
SD
See
AI, AO, DI and DO XXX NOT SETUP
Alarms.
SD
See
AI, AO, DI and DO XXX NOT SETUP
Alarms.
Owner's Manual for Power Zone Pro Sync

Advertisement

Table of Contents
loading

Table of Contents