Installation/Wiring Instructions
MODEL DB-11/-11E DETECTOR BASE
DB-11/-11E (NO REMOTE DEVICE)
+
TO INITIATING
1a
CIRCUIT OF
SBT, INC.
COMPATIBLE
CONTROL UNIT
(SEE CAUTION 1)
-
CAUTION:
1. Do not use looped wire under base terminal 5. Break wire
run to provide supervision of connection.
2. When a remote relay is used to control a critical system
function, the relay and its associated detector and optional
module(s) must be the ONLY devices on the initiating circuit.
Figure 1 Wiring Diagram for DB-11/-11E using PE-11, PE-11T, and DT-11 Detectors
DB-11/-11E (NO REMOTE DEVICE)
+
+
TO INITIATING
5
1a
CIRCUIT OF
SBT, INC.
6
1b
COMPATIBLE
CONTROL UNIT
-
-
Figure 2 Wiring Diagram for DB-11/-11E using FP-11, FPT-11, FS-DP , FS-DPT, and FS-DT Detectors
DB-11/-11E (NO REMOTE DEVICE)
LINE 1**
TO INITIATING
5
1a
CIRCUIT OF
SBT, INC.
6
1b
COMPATIBLE
CONTROL UNIT
LINE 2**
*The relay contacts are shown in the Non-Alarm/System Reset condition.
**HFP-11/HFPT-11 is a polarity insensitive detector. Line 1 and Line 2 can be either line of the loop.
Figure 3 Wiring Diagram for DB-11/-11E using HFP-11 and HFPT-11 Detectors
Siemens Building Technologies, Inc.
8 Fernwood Road
Florham Park, New Jersey 07932
1b
1b
5
6
+ +
OPTIONAL
REMOTE
ALARM
INDICATOR
MODELS
6
1a
RLI-1 / RLI-2
-
*The relay contacts are shown in the Non-Alarm/System Reset condition.
OPTIONAL
REMOTE
TB1
ALARM
INDICATOR
TB2
MODELS
RL-HW / RL-HC
TB3
Siemens Building Technologies, Ltd.
2 Kenview Boulevard
Brampton, Ontario, Canada L6T 5E4
DB-HR (REMOTE RELAY BASE)
SEE REMOTE DEVICE INSTRUCTIONS FOR WIRING DETAILS:
DEVICE
RR-11
6
RLC-11, RLW-11
RSAC-11, RSAW-11
5
If remote devices are supported by the initiating circuit, each detector/base may
have up to 2 remote devices with the following configurations and restrictions only:
Remote
Device 1
RR-11
RR-11
RLC-11, RLW-11
RLC-11, RLW-11
DB-11XRS (REMOTE RELAY BASE)
5+
RELAY*
NO
CONTACTS
C
6–
3A, 120 VAC
NC
3A, 30 VDC
-
DB-HR (REMOTE RELAY BASE)
5+
RELAY*
NO
CONTACTS
C
6–
3A, 120 VAC
NC
3A, 30 VDC
INSTALLATION
INSTRUCTIONS
P/N 315-094924
P/N 315-094925
P/N 315-094926
MULTIPLE REMOTE DEVICES
Remote
Device 2
Restrictions
RLC-11, RLW-11
See Caution 2
See Caution 2
RSAC-11, RSAW-11
RSAC-11, RSAW-11
Wire from base to
RLC-11, RLW-11
RSAC-11/RSAW-11 to RL-11
TO NEXT BASE
+ +
5
1a
6
1b
-
-
TO NEXT BASE
TO NEXT BASE
5
1a
6
1b
TO NEXT BASE
Model DB-11/-11E
(P/N 500-094151/500-094151E)
Fire Safety
END OF LINE DEVICE
(NOTE POLARITY
WHEN APPLICABLE)
1b
+
-
5
DO NOT
+
USE AN
END OF
LINE
DEVICE
5+
NO
C
6–
NC
DO NOT
USE AN
END OF
-
LINE
DEVICE
DO NOT
USE AN
END OF
LINE
DEVICE
5+
NO
C
6–
NC
DO NOT
USE AN
END OF
LINE
DEVICE

Advertisement

loading

Summary of Contents for Siemens DB-11

  • Page 1 TO NEXT BASE DEVICE *The relay contacts are shown in the Non-Alarm/System Reset condition. Figure 2 Wiring Diagram for DB-11/-11E using FP-11, FPT-11, FS-DP , FS-DPT, and FS-DT Detectors DB-11/-11E (NO REMOTE DEVICE) DB-HR (REMOTE RELAY BASE) TO NEXT BASE...
  • Page 2 Take up all slack in the outlet box. c. Properly dress and position all wires flat against the base. d. Check that screw terminals are tight. (DB-11 only) Break off the two mounting hole covers, and insert in two outer base mounting holes. Installation Instructions P/N 315-094193-7...

This manual is also suitable for:

Db-11e