4. CONTROLS
4.3.4 Unit Status Menu
When the Unit Status menu is highlighted, press the Rotate button to see following display:
Here you will find the following unit status points (Scroll down with the Rotate button):
•
Common Fault (Actual fault status)
•
Supply_Air_Temp (Actual supply air temperature)
•
Outdoor_Air_Temp (Actual outdoor temperature)
•
Evaporator_Temp (Actual temperature on the evaporator surface, only DanX HP)
•
Heating_Signal (Actual position of heating coil actuator, signal to electrical heating coil)
•
Heating_Coil_Pump (Actual status if pump is running)
•
Duct_Dampers (Actual outdoor / exhaust air damper position)
•
Bypass_Damper (Actual by pass damper position)
•
Compressor_Status (Compressor running or not, only on heat pump units)
•
Compressor_Test (Compressor test function)
•
Compressor_Stop (Manually stop function for compressor)
•
HP_LP_Alarm (Status of the HP/LP pressure switch)
•
Heat_Demand (Actual demand for heating in %. A demand < 50% means cooling
demand, > 50% means heating demand)
•
Dehumidify_Demand (Actual demand for dehumidification in %)
•
Room_Temp_CALC (Actual room temperature set point)
•
Room_Humidity_CALC (Actual room humidity set point
The points under Unit Status give an overall view of the actual running situation of the unit.
All points are read only for the user and can only be set into manual with the service
password.
21