4. CONTROLS
Unit_Status point. This point shows which current status the unit has. It can be either Open
/ Closed or Stop, depending on the time program TP1 and the setting of the function switch
point. This point can only be switched if you have a service technician password.
If you rotate the Rotate button further on, the start display will change again, now to the
following picture with two different menus; Set Points and Unit Status.
4.3.3 Set Point Menu
When the Set Point menu is highlighted, press the Rotate button and the following display
will appear:
Here you will find the following set points (if you cannot see them please scroll down by
rotating the Rotate button):
•
Temp_Open_Pool (Set point temperature in the pool hall when pool open)
•
Temp_Closed_Pool (Set point temperature in pool hall when pool closed)
•
Humid_Open_Pool (Set point humidity in the pool hall when pool open)
•
Humid_Closed_Pool (Set point humidity in pool hall when pool closed)
•
Supply_Fan_Low (Set point low air volume supply air fan)
•
Supply_Fan_High (Set point high air volume supply air fan)
•
Return_Fan_Low (Set point low air volume return air fan)
•
Return_Fan_High (Set point high air volume return air fan)
•
Min_Fresh_Air (Set point minimum fresh air amount)
•
Min_Supply_Temp (Set point minimum supply air temperature)
•
Max_Supply_Temp (Set point maximum supply air temperature)