4. CONTROLS

4.4.3 Interface Configuration (Modbus)

If you connected the DanX 1/2/3 to a BMS system via Modbus communication, you can
change the general Modbus settings under Interface Config. Scroll down to the point Modbus
and press the Rotate button.
You can now change the following settings:
Device ID (Set point for the number given to the unit)
Baud Rate (Set point baud rate)
Parity (Set point for parity)
No. Stop Bits (Set point for number of stop bits)
To make changes to the Modbus communication you must be logged in as installer (service
password).
For the different Modbus addresses please see Appendix 9.1.

4.4.4 System data

If the controller does not show the right time or date, you can change that under System
data.
All points beside Date / Time are for service use only and therefore not explained in this
manual. Highlight Date / Time and press the Rotate button and you will see the following
display.
30