4. CONTROLS
Open Low (When there is a signal from the PIR sensor the unit will go to Open Pool
mode with the fans in low speed)
Open High (When there is a signal from the PIR sensor the unit will go to Open Pool
mode with the fans in high speed)
If a pool cover switch is used, you should set the point Signal_TP_External in one of the
following three modes:
Closed Low (When there is a signal from the pool cover switch the unit will go in Closed
Pool mode with the fans in low speed)
Closed High (When there is a signal from the pool cover switch the unit will go in Closed
Pool mode with the fans in high speed)
Closed Stop (When there is a signal from the pool cover switch the unit will go in Closed
Pool mode with the fans stopped)
With the external signal set you must change the Unit Time Program in the following way:
Open the Unit_Time_Program and place the cursor on D1.
By now turning the Rotate button you change the program from D1 to Pool Closed if a PIR
sensor is connected, or Pool Open if a pool cover switch is connected. When you have done
that with Monday you have to do the same with all other days, so the Unit_Time_Program
would look like the following if you have connected a PIR sensor.
You can now go into the program Pool Closed to modify the fan speed when the unit is in
closed pool mode.