9. APPENDIX

9.2 Modbus register HP

Register
Register Name
40100
Room_Temp
40101
Supply_Temp
40102
Outdoor_Temp
40103
Room_Humidity
40104
Return_AirVolume
40105
Supply_AirVolume
40106
Duct_Dampers
40107
ByPass_Damper
40108
Heating_Signal
40109
Unit_Status
40110
Program_Status
40111
Open_Temp
40112
Closed_Temp
40113
Open_Humidity
40114
Closed_Humidity
40115
Min_Fresh_Air
40116
Return_Fan_High
40117
Return_Fan_Low
40118
Supply_Fan_High
40119
Supply_Fan_Low
40120
Max_Supply_Temp
40121
Min_Supply_Temp
40122
Evaporator_Temp
40150
Common_Fault
40151
Fan_Alarm
40152
CheckFilters
40153
Fire_Alarm
40154
HeatingCoil_Alarm
40155
Heating_Coil_Pump
40156
DX_Cooling
40157
External_Stop
40158
CompressorStatus
40159
HP_LP_Alarm
40160
WCC_Pump
40161
Time_Program
Type
Message Type
uint16
Read only
uint16
Read only
uint16
Read only
uint16
Read only
uint16
Read only
uint16
Read only
uint16
Read only
uint16
Read only
uint16
Read only
uint16
Read only
uint16
Read only
uint16
Read and Write
uint16
Read and Write
uint16
Read and Write
uint16
Read and Write
uint16
Read and Write
uint16
Read and Write
uint16
Read and Write
uint16
Read and Write
uint16
Read and Write
uint16
Read and Write
uint16
Read and Write
uint16
Read only
bool
Read only
bool
Read only
bool
Read only
bool
Read only
bool
Read only
bool
Read only
bool
Read only
bool
Read and Write
bool
Read only
bool
Read only
bool
Read only
bool
Read and Write
Scaling Factor
0,1 to be applied by Modbus Master
0,1 to be applied by Modbus Master
0,1 to be applied by Modbus Master
0,1 to be applied by Modbus Master
0,1 to be applied by Modbus Master
0,1 to be applied by Modbus Master
0,1 to be applied by Modbus Master
0,1 to be applied by Modbus Master
(0) Normal / (1) Alarm
(0) Normal / (1) Alarm
(0) Normal / (1) Alarm
(0) Normal / (1) Alarm
(0) Normal / (1) Alarm
(0) Off / (1) On
(0) Off / (1) On
(0) Auto / (1) Stop
(0) Off / (1) On
(0) Normal / (1) Alarm
(0) Off / (1) On
(0) MVC80 / (1) BMS
46
Mapped Datapoint
MB_Room_Temp
MB_Supply_Temp
MB_Outdoor_Temp
MB_Room_Humidity
Return_Airvolume
Supply_Airvolume
MB_Duct_Dampers
MB_ByPass_Damper
MB_Heating_Signal
UNIT_STATUS_OPEN
Program_Status
MB_Open_Temp
MB_Closed_Temp
MB_Open_humidity
MB_Closed_humidity
MB_Min_Fresh_Air
MB_Return_Fan_High
MB_Return_Fan_low
MB_Supply_Fan_High
MB_Supply_Fan_Low
MB_Max_Sup
MB_Min_Sup
MB_Evaporator_Temp
MB_Common_Fault
MB_Fan_Alarm
CheckFilters
MB_Fire_Alarm
MB_HeatCoilAlarm
MB_HeatCoilPump
MB_DX_Cooling
External_Stop
MB_CompStatus
MB_HP_LP_Alarm
MB_WCC_Pump
Time_Program