3. INSTALLATION

3.5.6 LPHW coil

The LPHW coil is connected in the following way:
Connect the water supply to the inlet of the coil.
Connect the water return to the outlet of the coil, so the water flow is always counter
flow.
Connect the two-way valve outside the unit to the water system, as shown in the
drawings.
After mounting the water valve, set the maximum flow for the coil on the valve (see
also separate instructions).
Install the actuator to the valve and connect it to the electrical panel (se electrical
diagram)
NB!
When connecting the heat exchanger, counter hold with a suitable tool in order to avoid any
damage to the pipes.

3.5.7 Frost thermostat for LPHW coil

In case a frost thermostat is installed, it is easier to do so before installing the supply air
duct. You will find the thermostat delivered separately in a plastic bag together with all
brackets needed.
Mount the frost thermostat on the top deck of the unit with the bracket delivered with
the thermostat.
Mount the bracket for the bulb after the heating coil in the duct outlet.
Take the duct and drill a hole, run the bulb with the capillary tube through the hole and
fasten the bulb to the bulb holder. Then mount the duct on the DanX unit.
The thermostat is prewired and the wire only must be connected to the main terminal
strip of the unit (see wiring diagram).
10