Read all instructions in this manual before installing. Perform steps in the order given. Failure to comply could result in severe personal injury, death, or substantial property damage. Thermal Solutions Products, LLC www.thermalsolutions.com Phone: 717-239-7642 1175 Manheim Pike, Lancaster, PA 17601...
Replacement Boiler Installations Draining and refilling the boiler & system Boiler Water Treatment VII. System Start-Up Concert Boiler Control Display Navigation System Check Power the Boiler Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Website: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
NOTICE NOTICE Indicates special instructions on installation, operation, or maintenance which are important but not related to personal injury hazards. Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Website: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
23” Between Boilers 16” 23” 23” * For Reverse Construction of the Arctic 1500 - 3000, the EL and the ER values are swapped Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Website: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
The condensate drain trap should be flushed valve. with water as part of your boiler maintenance schedule to remove any debris that might have accumulated over time. Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Website: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
No dimension for a round or CFH of natural gas at 7 PSI if internal switch rectangular opening shall be less than 3”. diaphragm ruptures. Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Website: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
Page 13
Ducts shall serve a single space. the mechanical air supply system is not in operation. Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Website: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
Page 14
Table 4, Table 6, and Table 7 shall be used to determine the ducted combustion air system equivalent length. c. Table Table 5 can be used for calculations. Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Website: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
Do not exceed maximum vent / combination air material having a fire resistance rating at least system length. equal to the rating of adjoining floor or ceiling. Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Website: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
CPVC or Radel (polyphenolsulfone) is prohibited. All condensate that forms in the vent must be able to drain back to the heat exchanger. Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Website: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
1. The total combustion air length plus the total vent length cannot exceed the maximum of 100 equivalent feet (30.48 Meters). 2. Combustion air and vent terminations do not count towards total equivalent length. Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Website: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
1. It is recommended to use tees for both intake and vertical terminatoins in extra windy locations. 2. All terminations shall have bird screens. 3. All non-metallic venting exposed to sunlight shall be UV resistant. Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Website: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
10. Do not locate the vent terminal under decks or venting systems is prohibited. similar structures. Covering non-metallic vent pipe and fittings with thermal insulation is prohibited. Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Website: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
2) In accordance with the current ANSI Z223.1/NFPA 54, National Fuel Gas Code 3) If locally adopted installation codes specify clearances different than those illustrated, then the most stringent clearance shall prevail. Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Website: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
Vent and intake piping must not share the same gooseneck All terminations should have Bird/Rodent Screens Do not use rain caps, Rain will drain through boot tee or condensate drain Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Website: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
Extend combustion air pipe to maintain minimum vertical and horizontal distance of 12 in (300 mm) from roof surface or from the maximum snow level. Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Website: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
Recirculation of flue gas products into the combustion air supply can cause damage to property or the appliance. Figure 9: Slopped Roof Termination Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Website: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
"Engineered Venting Method" section in this extend the distance from building surfaces to vent manual. termination end and increase the horizontal distance between adjacent vent terminations Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Website: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
4. Adhere to the minimum and maximum wall and airtight. thickness specified by the manufacturer of the wall penetration assembly. Alteration of the appliance vent connection is prohibited. Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Website: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
5. It is recommended to use tee terminations with a vertical run in extra windy areas. Figure 11: Multiple Appliance Direct Vent Termination Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Website: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
If polypropylene liner is 48 ft. (14.6 m). contaminants cannot be removed, do not use room air for combustion. Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Website: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
Page 34
This boiler operates at a positive vent pressure. v. A factory-built chimney used for venting an appliance shall be certified. Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Website: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
Do not insulate polypropylene vent pipes. Excessive heat could cause premature vent pipe failure. Figure 12: Flexible Vent in Masonry Chimney with Separate Combustion Air Intake Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Website: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
Page 37
The “special venting systems” shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions. Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Website: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
1.25 10.7 FLA = Full Load Amps : CCA = Control Circuit Amps : MHP = Motor Horse Power : MA = Motor Amps Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Website: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
Contact a qualified boiler water chemical treatment company for their recommendations. See Section VI, Step ""E. Boiler Water Treatment" for more information. Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Website: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
Always follow the safety precautions on the container's label. Add chemicals slowly and in small amounts to prevent excessive heat and agitation. Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Website: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
When filling the system, provide chemical treatment as outlined in section "E. Boiler Water Treatment". Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Website: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
Dissolved oxygen will cause severe system corrosion. Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Website: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
NOTICE NOTICE Refer to the Concert Boiler Control manual for detailed instructions on the use of the hydronic control and display. Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Website: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
4. Cycle the boiler. The boiler should lockout on gas pressure failure. In this case it should be the low gas pressure switch. Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Website: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
Page 46
For boilers specified to be less than 9 ppm ii. Remove brass hex cover from front center NOx adjust the O level within 7.0% to 9.0%. of regulator. Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Website: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
20% to 100% and the intermediate points in between as many times as required, repeating Step 21 as necessary. Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Website: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
Contact the boiler manufacturer or a qualified heating service technician if the boiler has failed to light consecutively three times after initially resetting the Concert boiler control. Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Website: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
Never jump out or bypass any safety or operating control or components of this boiler. Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Website: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
3. Remove any excess oxide deposits from the surface of the igniter with steel wool Do not use sandpaper, emery cloth or scotch brite pads. Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Website: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
H. Heat Exchanger Cleaning 1. Perform visual inspection of both boiler flue passes, and remove any debris from the surfaces of the heat exchanger. Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Website: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
6. Pull upper tube-end. Repeat the procedure to the pull the tube-end of the same tube from the upper header. Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Website: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
The tone will also change from a “Ting” sound to more of a “Tong” sound. This indicates the tube has seated. Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Website: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
Page 57
Do Not Overdrive Tubes! Overdriving tubes can cause damage to the tubes and boiler header holes. Use only approved Thermal Solutions tube driver and specified hammer. The end-formed tube fitting is designed to deform if overdriven to minimize damage to the vessel tube holes.
For High Turndown Arctic 1500-6000 boilers display issues, contact you Sales Rep for the latest PLC and Display updates. If you don't know who your sales rep is, call the number listed at the bottom of the page. Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Website: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
Poor Combustion Remove the boiler’s side panels and check for flue gas leakage around Leakage the heat exchanger, burner mounting plate, and blower transition piece. Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Website: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
1030 1820 3720 1700 3460 Based on gas pressures less than 2 psig and a pressure drop of 3.0 iwc and 0.6 specific gravity. Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Website: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
Equivalent lengths are for standard screwed fittings and for screwed, flanged, and welded valves relative to schedule 40 steel. Table 34: Specific Gravity Correction Factors Specific Correction Factor Specific Gravity Correction Factor Gravity 1.04 Propane Butane Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Website: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
Remove leads and turn the air switch adjustment an additional, one full turn clockwise. v. Reset Parameters 502:00 (Air) and 503:00 (VSD) back to “0”. Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Website: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
Refer to the manufactures' installation instructions. 4. Circulation pump must be sized to overcome the pressure drop across the entire loop. Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Website: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
Refer to the manufactures' installation instructions. 4. Circulation pump must be sized to overcome the pressure drop across the entire loop. Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Website: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
Refer to the manufactures' installation instructions. 4. Circulation pump must be sized to overcome the pressure drop across the entire loop. Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Website: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
Refer to the manufactures' installation instructions. 4. Circulation pump must be sized to overcome the pressure drop across the entire loop. Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Website: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
3. Some piping components cannot be supported by the pipping. Refer to the manufactures' installation instructions. 4. Circulation pump must be sized to overcome the pressure drop across the entire loop. Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Website: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
Note: Wiring diagrams are for reference only, please refer to the wiring shipped with the boiler for accuracy Figure 30: Arctic 1000 Wiring Diagram Page 1-A Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Website: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
Figure 31: Arctic 1500 To Arctic 3000 115 VAC Single Phase Wiring Diagram Note: Wiring diagrams are for reference only, please refer to the wiring shipped with the boiler for accuracy Page 1-A Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Website: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
Figure 32: Arctic 1500 To Arctic 3000 208 – 230 VAC Single Phase Wiring Diagram Note: Wiring diagrams are for reference only, please refer to the wiring shipped with the boiler for accuracy Page 1-A Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Website: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
Figure 33: Arctic 2000 To Arctic 3000 208-460 VAC Three Phase Wiring Diagram Note: Wiring diagrams are for reference only, please refer to the wiring shipped with the boiler for accuracy Page 1-A Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Website: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
Three Phase Wiring Diagram Note: Wiring diagrams are for reference only, please refer to the wiring shipped with the boiler for accuracy Page 1-A Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Website: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
Figure 35: Arctic 1500 To Arctic 3000 Dual Fuel 120-460 VAC Single or Three Phase Wiring Diagram Note: Wiring diagrams are for reference only, please refer to the wiring shipped with the boiler for accuracy Page 1-A Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Website: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
Figure 36: Arctic 3500 To Arctic 6000 208-460 VAC Three Phase Wiring Diagram Note: Wiring diagrams are for reference only, please refer to the wiring shipped with the boiler for accuracy Page 1-A Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Website: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
Figure 37: Arctic 3500 To Arctic 6000 Dual Fuel 208-460 VAC Three Phase Wiring Diagram Note: Wiring diagrams are for reference only, please refer to the wiring shipped with the boiler for accuracy Page 1-A Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Website: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...