5. A copy of all installation instructions for all
Product Approved sidewall horizontally vented
gas fueled equipment, all venting instructions,
all parts lists for venting instructions, and/or all
venting design instructions shall remain with
the appliance or equipment at the completion
of the installation.
38
Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Website: www.thermalsolutions.com
Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com
V. Requirements
A. Electrical
 WARNING
WARNING
All electrical connections must conform to the
National Electrical Code, ANSI / NFPA 70 and / or
CSA C22.1 Electrical Code and all other State and
Local codes.
A separate electrical circuit must be run from
the main electrical service with an over-current
device/disconnect in the circuit. A service switch is
recommended and may be required by some local
jurisdictions. Locate the service switch such that the
appliance can be shut off without exposing personnel
to danger in the event of an emergency. See Table 17
for available voltages.
Table 17: Electrical Requirements
Voltage
FLA
120/1/60
6.6
Voltage
FLA
120/1/60
13.1
208-240/1/60
6.9
Arctic 2000 to Arctic 3000
Voltage
FLA
120/1/60
15.6
208-240/1/60
8.3
208-240/3/60
9.5
480/3/60
5.25
Arctic 3500 to Arctic 4000
Voltage
FLA
208-240/3/60
10.5
480/3/60
5.25
Arctic 4500 to Arctic 6000
Voltage
FLA
208-240/3/60
26.6
480/3/60
14.25
FLA = Full Load Amps : CCA = Control Circuit Amps : MHP = Motor
Horse Power : MA = Motor Amps
Arctic 1000
CCA
MHP
2.6
.46
Arctic 1500
CCA
MHP
2.6
1.1
2.6
1.1
CCA
MHP
2.6
1.5
2.6
1.5
2.6
3
1.25
3.2
CCA
MHP
2.6
3
1.25
3.2
CCA
MHP
2.6
10.7
1.25
10.7
MA
4
MA
10.5
4.3
MA
13
5.7
6.9
4
MA
6.9
4
MA
24
13