Post these instructions and maintain in legible condition. NOTICE Indicates specific instructions installation, operation, or maintenance, which are important but not related to personal injury hazards. Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Web: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
18. Temperature Display. Provides for temperature set points and actual temperature. Figure 2: ARC1500 - 3000 External Boiler Connections and Components Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Web: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
See Figure 4 and Table 2 for minimum and service. clearances to walls, ceilings, or obstructions. These clearances are intended as a general Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Web: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
All boilers must be installed in a space that is large compared to the boiler. Figure 4: Clearances and Serviceability Flue Gas Vent Boiler Boiler Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Web: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
The shipping feet/legs MUST BE PLUG THIS RELIEF VALVE. REMOVED after the boiler is set in-place on its concrete foundation before any piping/electrical connections are made. It is Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Web: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
A common condensate pump/sump may be 3.2.6.1 ARC1000 Condensate Drain Trap used. Run separate piping from each condensate drain to the sump. A common Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Web: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
Movable combustion air dampers, automatic or manually adjustable, must be electrically interlocked with the boiler to prevent boiler operation if the dampers are closed. Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Web: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
BOCA, National Mechanical Code 4. Vent pipe system shall be acceptable for use with boiler fuel type. Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Web: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
Page 17
The fire-stop must close the opening between the vent pipe and the structure. 12. Appendix B shall be used to determine the vent system equivalent length. Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Web: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
6. It is recommended that combustion air be taken from the boiler room. Follow the Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Web: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
/ or death. Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Web: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
Page 20
248 CMR The referenced “special venting 5.08(2)(a)1 through 4: system” instructions shall be included with the appliance or Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Web: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
Ventilation Air: an opening for ventilation air open position. at the highest point that opens to the outdoors shall provide Ventilation of the Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Web: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
A flue gas vent or a vent connector shall not be installed in either a duct or a shaft used for return air, hot air, ventilating air, or combustion air. Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Web: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
Further, an air vent should be installed at all high points throughout the piping system. Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Web: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
Table 9 Maximum Water Flow Rates for Variable Primary Pumping WARNING Do not use Table 8 or Table 9 to size a constant volume pump. Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Web: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
Flush the system clean, being certain to isolate amounts to prevent excessive heat and the boiler. agitation. WARNING Do not flush the system through the boiler. Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Web: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
Air vents sticking and leaking Frequent relief valve operating the system see section 3.8. Piping leaks at joints Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Web: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
Table 15 Recommended Feed Water conditions may indicate. Limits See Table 14 for examples of typical chemical agents found in untreated water along with their potential effects. Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Web: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
NOTICE Refer to the Concert Boiler Control manual for detailed instructions on the use of the hydronic control and display. Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Web: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
Appendix C. 28. Perform tests on each of the components listed in Table 16. Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Web: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
Reduce the water flow rate with a manual Adjust manual valve to Water Flow Switch Low Water Flow shutoff valve until the normal position. boiler shuts down. Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Web: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
Assure that all gas valves and electrical disconnect switches are off before attempting any disassembly or service. Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Web: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
Igniter Gasket Burner Assembly Cleaning 1. After disconnecting power to the boiler, remove the boiler’s furnace door. For part identification, refer to the “Parts Manual”. Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Web: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
2. Use the proper tools. Use the following tools to remove and replace leaking boiler tubes: a. Tube Puller (P/N 106019-02) b. Tube Driver (P/N 106019-01) c. Sledgehammer (steel head, approximately 3 lb) Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Web: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
3. Clear tube-end from the header. Continue driving wedge under and leveraging flange up until it pops the end of the tube free from the hole in the header. Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Web: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email:...
The tone will also change from a “ting” sound to more of a “tong” sound. This indicates the tube has seated. Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Web: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
Do not install, operate, service or repair any components of this equipment unless you are qualified and fully understand all requirements and procedures. Trained personnel should refer to those who have completed Thermal Solutions Service School training specific to this product.
Select display Help icon and review Limit String or temperature is “Standby” and Status. greater than “Priority” shows setpoint. Central Heat or Domestic Hot Water. Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Web: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
Page 44
Check for loose or defective display harness, Communication Communication defective display or defective control. Error 3 Fault. Refer to Concert Boiler Control manual for more details. Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Web: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
Page 45
Poor Combustion Remove the boiler’s side panels and check for flue gas leakage around the heat exchanger, burner Leakage mounting plate, and blower transition piece. Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Web: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
3720 1030 1820 3460 1700 Based on gas pressures less than 2 psig and a pressure drop of 3.0 iwc and 0.6 specific gravity. Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Web: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
Equivalent lengths are for standard screwed fittings and for screwed, flanged, and welded valves relative to schedule 40 steel. Table 21: Specific Gravity Correction Factors Specific Gravity Correction Factor Specific Gravity Correction Factor 1.04 Propane Butane Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Web: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
Appendix F Boiler Piping Diagrams – Typical Layout for all Boiler Models (Boilers may look different than pictured) Appendix F.1 Single Boiler, Primary / Secondary Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Web: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email:...
Page 62
9.42 12.08 12.33 16.50 16.83 23.83 24.25 37.25 37.92 Delta T’s are based on the maximum output with a nominal boiler efficiency of 95%. Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Web: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
Form: 2435-3 Arctic Installation and Operation Manual Revision: 10 P/N 105641-01 Date: 12-1-2018 Appendix H.5 ARC3500 To ARC6000 208-460 VAC Three Phase Wiring Diagram Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Web: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
Page 72
Arctic Installation and Operation Manual Revision: 10 P/N 105641-01 Date: 12-1-2018 Wiring diagrams are for reference only, please refer to the wiring shipped with the boiler for accuracy. Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Web: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
Page 73
Thermal Solutions, P.O. Box 3244, Lancaster, PA 17604-3244), in writing, within the Warranty Period, providing a detailed description of all FLUE GAS CORROSION WARRANTY Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Web: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...
Page 74
Contrary to the written instructions furnished with the unit. Adverse local conditions in general and, specifically, sediment or lime precipitation in Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Web: www.thermalsolutions.com Phone: 717-239-7642 Fax: 877-501-5212 Email: sales@thermalsolutions.com...