5.12

Light oil supply

Explosion danger due to fuel leaks in the pres-
ence of a flammable source.
Precautions: avoid knocking, attrition, sparks and
heat.
Make sure that the fuel interception tap is closed
before performing any operation on the burner.
The fuel supply line must be installed by qualified
personnel, in compliance with current standards
and laws.
WARNING
5.12.1 Double-pipe circuit
The burner is equipped with a self-priming pump which is capable
of feeding itself within the limits listed in Tab. J.
Tank higher than burner A (Fig. 19)
Distance "P" must not exceed 10 meters in order to avoid strain-
ing the pump's seal; distance "V" must not exceed 4 meters in or-
der to allow pump self-priming even when the tank is almost
empty.
Tank lower than burner B (Fig. 19)
Pump depression values higher than 0.45 bar (35 cm Hg) must
not be exceeded because at higher levels gas is released from
the fuel, the pump starts making noise and its working life-
span decreases.
It is good practice to ensure that the return and suction lines enter
the burner from the same height; in this way it will be less proba-
ble that the suction line fails to prime or stops priming.
Key (Fig. 19)
H = Pump/Foot valve height difference
Ø = Inside pipe diameter
1 = Burner
2 = Pump
3 = Filter
4 = Manual on/off valve
5 = Suction line
6 = Foot valve
7 = Quick closing manual valve with remote control (Italy only)
8 = On/off solenoid valve (Italy only). See electrical layout.
Connections to be carried out by the installer (SV).
9 = Return line
10 = Check valve (only Italy)
20170641
Installation
5.12.2 Loop circuit
A loop circuit consists of a loop of piping departing from and re-
turning to the tank with an auxiliary pump that circulates the fuel
under pressure. A branch connection from the loop feeds the
burner.
This circuit is extremely useful whenever the burner pump does
not succeed in self-priming because the tank distance and/or
height difference are higher than the values listed in Tab. J.
RLS 1000/E FGR
+/- H
[m]
20
22
4.0
26
45
3.0
22
39
2.0
18
33
1.0
15
26
0.5
13
23
0
11
20
-4.0
-
-3.0
-
-2.0
-
-1.0
7
14
-0.5
9
17
0
11
20
20053391
22
GB
RLS 1200/E FGR
Ø [mm]
24
27
22
73
138
19
63
120
16
53
102
13
44
84
10
39
75
9
34
66
7
-
-
-
-
-
-
12
-
7
14
30
-
24
48
-
29
57
5
34
66
7
Ø [mm]
24
27
36
33
65
300
28
55
260
23
45
220
18
38
185
16
33
165
13
30
145
-
-
-
-
-
30
-
11
70
9
20
108
11
25
125
13
29
145
Tab. J
Fig. 19