Hydraulic system

6.1

Light oil supply

Explosion danger due to fuel leaks in the
presence of a flammable source.
Precautions: avoid knocking, attrition, sparks and
heat.
Make sure the fuel shut-off valve is closed before
performing any operation on the burner.
The fuel supply line must be installed by qualified
personnel, in compliance with current standards
and laws.
ATTENTION
DOUBLE-PIPE CIRCUIT (A)
The burner is equipped with a self-priming pump which is capable
of feeding itself within the limits listed in the table at the side.
The tank is higher than the burner A
The distance "P" must not exceed 10 meters in order to avoid
subjecting the pump seal to excessive strain; the distance V must
not exceed 4 meters in order to permit pump self-priming even
when the tank is almost completely empty.
The tank is lower than the burner B
Pump depression values higher than 0.45 bar (35 cm Hg) must
not be exceeded. Because at higher levels gas is released from
the fuel; the pump becomes noisy and its lifetime is shortened.
It is good practice to ensure that the return and suction lines enter
the burner from the same height; the suction line is more difficult
to disconnect.
LOOP CIRCUIT
The loop circuit is composed of a duct starting from the tank and
going back to it, in which an auxiliary pump makes the
pressurised fuel flow. A branch from the loop supplies the burner.
This circuit is extremely useful whenever the burner pump does
not succeed in self-priming because the tank distance and/or
height difference are higher than the values listed in Tab. I.
RL 28/M
+/- H
L (metres)
ø 10
ø 12
(metres)
mm
mm
+ 4.0
63
144
+ 3.0
55
127
+ 2.0
48
111
+ 1.0
40
94
+ 0.5
37
86
0
33
78
- 0.5
29
70
- 1.0
25
62
- 2.0
17
45
- 3.0
10
29
- 4.0
-
12
Hydraulic system
RL 38-50/M
L (metres)
ø 14
ø 10
ø 12
ø 14
mm
mm
mm
mm
150
51
112
150
150
45
99
150
150
39
86
150
150
32
73
144
150
29
66
132
150
26
60
120
133
23
54
108
118
20
47
88
13
34
58
7
21
28
-
8
Tab. I
7 7
10
9
6
7
6
Key (Fig. 19)
H = Pump/Foot valve height difference
L = Piping length
Ø = Inside pipe diameter
1 = Burner
2 = Pump
3 = Filter
4 = Manual on/off valve
5 = Suction line
6 = Foot valve
7 = Quick closing manual valve with remote control (Italy only)
8 = On/off solenoid valve (Italy only)
9 = Return line
10 = Check valve (Italy only)
96
71
46
21
19
GB
A
5
1
8
4
5
3
9
B
20170883
2
Fig. 19
20167399