EMC Type Tests
61000-4-2
61000-4-3
61000-4-4
61000-4-5
61000-4-6
61000-4-8
61000-4-9
61000-4-11
61000-4-16
61000-4-17
61000-4-18
61000-4-29
RUGGEDCOM RST916P
Equipment Manual, 11/2023, C79000-G8976-1489-06
Test
IEC
ESD
IEC
Radiated RFI
IEC
Burst (Fast Transient)
IEC
Surge
IEC
Induced (Conducted) RFI
IEC
Magnetic Field
IEC
Pulse Magnetic Field
IEC
Voltage Dips and Interrupts
IEC
Mains Frequency Voltage
IEC
Ripple on DC Power Supply
IEC
Damped Oscillatory Wave
IEC
Voltage Dips and Interrupts
6.2 EMC and Environmental Type Tests
Description
Enclosure
Contact
Enclosure Air
Enclosure
Ports
Signal Ports
DC Power
Ports
AC Power
Ports
Earth
Ground Ports
Signal Ports
DC Power
Ports
AC Power
Ports
Signal Ports
DC Power
Ports
AC Power
Ports
Earth
Ground Ports
Enclosure
Ports
Enclosure
Ports
AC Power
Ports
Signal Ports
DC Power
Ports
DC Power
Ports
Slow
Damped
DC Power
Ports
Test Levels
± 8 kV
± 15 kV
20 V/m
± 4 kV @ 2.5 kHz, 5 kHz
± 4 kV @ 2.5 kHz, 5 kHz
± 4 kV @ 2.5 kHz, 5 kHz
± 4 kV @ 2.5 kHz, 5 kHz
± 4 kV Line-to-Ground
± 2 kV Line-to-Line
± 2 kV Line-to-Ground
± 1 kV Line-to-Line
± 4 kV Line-to-Ground
± 2 kV Line-to-Line
10 V
10 V
10 V
10 V
100 A/m Continuous
1000 A/m for 1 s
300 A/m
30% for 0.5 Cycles
60% for 5 Cycles
100% for 250 Cycles
30 V Continuous
300 V for 1 s
30 V Continuous
300 V for 1 s
15%
2.5 kV Common
100 kHz or 1 MHz
30% for 0.1 s
60% for 0.1 s
Certification
Severity
Levels
4
4
4
4
4
4
4
3
4
3
3
3
3
 
4
 
4
4
4
3
 