5.3.6 Timer T

(1) The 100ms timer, 10ms timer and 100ms integrated timer are available for this count-up type
timer.
100ms Timer T
(a) When the input conditions are set, the count starts. When the set value is counted, that timer
contact will turn ON.
(b) If the input conditions are turned OFF, the 100ms timer count value will be set to 0, and the
contact will turn OFF.
X5
Input conditions
(c) The value is set with a decimal, and can be designated from 1 to 32767 (0.1 to 3276.7 s). The
data register (D) data can also be used as the setting value. File register (R) cannot be used.
10ms Timer T
(a) When the input conditions are set, the count starts. When the set value is counted, that timer
contact will turn ON.
(b) If the input conditions are turned OFF, the 10ms timer count value will be set to 0, and the
contact will turn OFF.
X5
Input conditions
(c) The value is set with a decimal, and can be designated from 1 to 32767 (0.01 to 327.67 s). The
data register (D) data can also be used as the setting value. File register (R) cannot be used.
5. Explanation of Devices
5.3 Detailed Explanation of Devices
X5
T57 K50
T57 coll
T57 contact OFF
100ms timer
X5
T1 K500
T1 coll
10ms timer
T1 contact OFF
- 67 -
Get other manuals https://www.bkmanuals.com
ON
OFF
ON
5 seconds
OFF
ON
ON
OFF
ON
OFF
5 seconds
ON