5 Use and operation
5.3.1 Heating circuit output test
The available electrical outputs can be switched
on/off directly using the button. Can be used to test
the function of individual components.
ATTENTION: Only to be undertaken by qual-
!
ified personnel.
5.4 Customer menu
1 Required boiler values
2 Vacuum output
> 15
14
> 14
3 Heat exchanger cleaning
4 User lock
> 16
[1]
5 Message log
: Recording of alarm and noti-
fication messages
6 Operating hour counter
7 Boiler output test (ATTENTION: Only to be
undertaken by qualified personnel).
8 Qualified personnel menu
9 Customer trend (USB stick essential)
11 Cascade settings (optional)
[1] Button is only visible if a message is active.
5.4.1 Required boiler values
Burner release time
1
The burner can start within the release times; outside
of these times, starting does not take place and/or the
burner is stopped. A time release from 00:00 to 23:59
means that no restriction is pending and the burner
may start at any time.
ATTENTION - In order to protect against frost,
!
only automatic start-up of the heating circuit
pump is active outside the release time.
i
DHW heating in summer
If the boiler is used for heating hot water, the
required chimney draught of 5 Pa may not be
present in the summer months (or outside the
heating period). This may result in smoke
escaping in the boiler room.
Reason: High temperature on the chimney
stack (greater than 30°C); as a result, the
cooler air does not rise (~ 20°C air tem-
perature when the burner starts) in the chim-
ney.
Remedy: Set the burner time release from
00:00 to 07:00 or from 21:00 to 23:59.
Operation manual ecotop-zero, ecotop-light
> 15
> 16
> 17
> 18