ABB AC500-eCo V3 Manual page 70

Hide thumbs Also See for AC500-eCo V3:
Table of Contents

Advertisement

Device specifications
Processor modules > PM50xx
Table 6: Pin assignment of the Ethernet interface
Interface
6.1.1.4
Power supply
The processor modules PM50xx can be connected to the 24 V DC supply voltage via a remov-
able 3-pin spring terminal block or a 3-pin screw terminal block.
Table 7: Removable terminal block for the supply voltage 24 V DC
The terminal block is available as a set for AC500-eCo V3 processor modules.
Basic CPU (PM5012)
Spring type
TA5211-TSPF-B
Further information on the terminal blocks concerning power supply and onboard inputs/outputs
are provided under
on page 149.
70
Pin
1
2
3
4
5
6
7
8
Shield
3-pin spring terminal block
Screw type
TA5211-TSCL-B
Ä Chapter 6.3.3 "Pluggable connectors for screw and spring connection"
3ADR010635, 2, en_US
Description
Tx+
Tx-
Rx+
NC
NC
Rx-
NC
NC
Cable shield
3-pin screw terminal block
Standard CPUs (PM5032, PM5052) and
Pro CPUs (PM5072)
Spring type
TA5212-TSPF
Transmit Data +
Transmit Data -
Receive Data +
Not connected
Not connected
Receive Data -
Not connected
Not connected
Functional earth
Screw type
TA5212-TSCL
2021/06/29