Parameter
Indication of the input signals
Monitoring point of input indicator
Input type according to EN 61131-2
Input signal range
Signal 0
Undefined signal
Signal 1
Ripple with signal 0
Ripple with signal 1
Input current per channel
Max. permissible leakage current (at 2-wire proximity
switches)
Input delay (0->1 or 1->0)
Input data length
Max. cable length
6.2.3.8.2
Technical data of the digital outputs
Parameter
Number of channels per module
Distribution of the channels into groups
Connection of the channels O0 to O1
Reference potential for the channels O0 to O17
Common power supply voltage
Indication of the output signals
Monitoring point of output indicator
Way of operation
Min. output voltage at signal 1
2021/06/29
Input voltage +24 V
Input voltage +5 V
Input voltage +15 V
Input voltage +30 V
Shielded
Unshielded
3ADR010635, 2, en_US
Option boards > TA5110-2DI2DOT - Digital input/output module option board
Value
2 transistor outputs (24 V DC, 0.5 A max.)
1 group of 2 channels
Terminals 4 to 5
Terminal 7 (negative pole of the process
voltage, name ZP)
Terminal 6 (positive pole of the process
voltage, name UP)
1 yellow LED per channel; the LED is on
when the output signal is high (signal 1)
and the module is powered via the I/O bus
Controlled together with transistor
Non-latching type
UP - 0.1 V
Device specifications
Value
1 yellow LED per channel; the
LED is ON when the input signal
is high (signal 1)
LED
It is not part of input circuit (its
controlled by processor side, not
process side)
Type 1 source
Type 1 sink
-24 V DC
+24 V DC
-5 V...+3 V
-3 V...+5 V
-15 V...+ 5 V
+5 V...+15 V
-30 V...-15 V
+15 V...+30 V
-5 V...+3 V
-3 V...+5 V
-30 V...-15 V
+15 V...+30 V
Typ. 5 mA
Typ. 1 mA
< 3 mA
< 7 mA
1 mA
Typ. 8 ms
1 byte
500 m
300 m
123