Device specifications
Option boards > TA5110-2DI2DOT - Digital input/output module option board
The following block diagram shows the internal construction of the digital inputs and outputs:
Table 25: Assignment of the terminals:
Terminal
1
2
3
4
5
6
7
The internal power supply voltage for the module's circuitry is carried out via the connection to
CPU. Thus, the current consumption from 24 V DC power supply at the terminals L+ and M of
the CPU module increases by 10 mA per TA5110-2DI2DOT.
The external power supply connection is carried out via the UP (+24 V DC) and ZP (0 V DC)
terminals.
118
Signal
COM 0..1
I0
I1
O0
O1
UP
ZP
WARNING!
Removal/Insertion under power
The devices are not designed for removal or insertion under power. Because of
unforeseeable consequences, it is not allowed to plug or unplug devices with
the power being ON.
Make sure that all voltage sources (supply and process voltage) are switched
off before you
connect or disconnect any signal or terminal block
remove, mount or replace a module.
Disconnecting any powered devices while energized in a hazardous location
could result in an electric arc, which could create a flammable ignition resulting
in fire or explosion.
Make sure that power is removed and that the area has been thoroughly
checked to ensure that flammable materials are not present prior to proceeding.
The devices must not be opened when in operation. The same applies to the
network interfaces.
3ADR010635, 2, en_US
Description
Input common for signals I0 to I1
Input signal I0
Input signal I1
Output signal O0
Output signal O1
Process supply voltage UP +24 V DC
Process supply voltage ZP 0 V DC
2021/06/29