Device specifications
Option boards > TA5110-2DI2DOT - Digital input/output module option board
6.2.3.7
State LEDs
LED
Inputs I0...I1
Outputs O0...O1
6.2.3.8
Technical data
The system data of AC500-eCo V3 apply
on page 154
Only additional details are therefore documented below.
Parameter
Process supply voltage UP
Current consumption from 24 V DC power supply
at the L+/M terminals of the CPU
Galvanic isolation
Isolated groups
Surge-voltage (max.)
Max. power dissipation within the module
Weight
Mounting position
Cooling
6.2.3.8.1
Technical data of the digital inputs
Parameter
Number of channels per module
Distribution of the channels into groups
Connections of the channels I0 to I1
Reference potential for the channels I0 to I1
122
State
Digital input
Digital output
Connections
Rated value
Current consumption via UP terminal
Max. ripple
Inrush current
Protection against reversed voltage
Rated protection fuse for UP
3ADR010635, 2, en_US
Color
LED = OFF
Yellow
Input is OFF
Yellow
Output is OFF
Ä Chapter 6.4 "System data AC500-eCo V3"
Value
Terminal 6 for UP (+24 V DC) and ter-
minal 7 for ZP (0 VDC)
24 V DC
5 mA + max. 0.5 A per output
5 %
0.000002 A²s
Yes
Recommended; the outputs must be pro-
tected by an 3 A fast fuse
Ca. 10 mA
Yes, between the input group and the
output group and the rest of the module
2 groups (1 group for 2 input channels, 1
group for 2 output channels)
35 V DC for 0.5 s
0.7 W
ca. 120 g
Horizontal or vertical
The natural convection cooling must not
be hindered by cable ducts or other parts
in the switch-gear cabinet.
Value
2
1 group for 2 channels
Terminals 2 to 3
Terminal 1
LED = ON
Input is ON
Output is ON