Table 13: Assignment of the terminals for PM5032-R-ETH and PM5052-R-ETH:
Terminal
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
Block diagrams
The following block diagram shows the internal structure of the onboard I/Os.
2021/06/29
Signal
Description
COM 0..11
Input common for digital input signals DI0 to DI11
I0
Digital input signal DI0 (5 kHz)
I1
Digital input signal DI1 (5 kHz)
I2
Digital input signal DI2 (5 kHz)
I3
Digital input signal DI3 (5 kHz)
I4
Digital input signal DI4 (100 kHz)
I5
Digital input signal DI5 (100 kHz)
I6
Digital input signal DI6 (100 kHz)
I7
Digital input signal DI7 (100 kHz)
I8
Digital input signal DI8
I9
Digital input signal DI9
I10
Digital input signal DI10
I11
Digital input signal DI11
NO0
Normally-open relay contact of the output NO0
NO1
Normally-open relay contact of the output NO1
NO2
Normally-open relay contact of the output NO2
R0..2
Output common for signals NO0 to NO2
NO3
Normally-open relay contact of the output NO3
NO4
Normally-open relay contact of the output NO4
NO5
Normally-open relay contact of the output NO5
R3..5
Output common for signals NO3 to NO5
C12
Digital input/output signal configurable DC12 (100 kHz,
if configured as output)
C13
Digital input/output signal configurable DC13 (100 kHz,
if configured as output)
UP
Process supply voltage UP +24 V DC
ZP
Process supply voltage ZP 0 V DC
3ADR010635, 2, en_US
Device specifications
Processor modules > PM50xx