Device specifications
Processor modules > PM50xx
6.1.1.7.4
Internal data exchange
Parameter
Digital inputs (bytes)
Digital outputs (bytes)
6.1.1.7.5
I/O configuration
The configuration data of the onboard I/Os is stored in the processor modules PM50xx. See
PLC configuration:
6.1.1.7.6
Parameterization
For information about parameterization, refer to the description for onboard I/Os for processor
modules PM50xx. See PLC configuration: and
6.1.1.7.7
Diagnosis
Class Comp Dev
Class Inter-
Device Module
face
Errors for Onboard I/O
Light errors
3
8
255
3
8
255
Warnings
86
CAUTION!
Risk of damaging the processor module!
Never short-circuit or overload the outputs.
Never connect inductive loads without an external suppression against
voltage peaks due to inductive kickback.
Never connect voltages > 240 V. All outputs must be fed from the same
phase.
Use an external 5 A fast protection fuse for the outputs.
Mod
Ch
Err
Channel Error-
Identifier
2
0
3
3
0
26
3ADR010635, 2, en_US
Value
On request
On request
PS501 PLC Browser
Error message
MaxWaitRun for onboard I/O
module has expired, when PLC
is put into RUN state
Invalid configuration of onboard
I/O module, e. g. 2 input chan-
nels are configured as fast
counter and interrupt input at
the same time.
<− Display in
Remedy
Reboot and try it
again. If the error
still exists, replace
processor module
for testing
Correct PLC con-
figuration
2021/06/29