Configuration
October 2023
88
d) Click Service Tools → Variables → Path Information tab to view the device's
chord performance (%), Gain (dB), SNR (dB), Signal (mV) and Noise (mV).
e) Click Service Tools → Variables → Flow Totals to view the volume totals
(forward and reverse Uncorrected Volume) parameters for the connected
device.
f) Click Service Tools → Variables → All Variables tab to view Primary,
Secondary, Third and Fourth Variable parameter status.
Figure 4-17: AMS Device Manager - Service Tools All Variables
Gauges display each variable's status as good or bad. If a status is bad refer
to the Service Tools Alerts page for recommended actions to resolve the alert
condition. Also refer to the
48 and 140 details.
Important
Alerts are triggered for Command 48 Additional device status and Command
140 detailed status information. Alerts are grouped as Failed - Fix Now,
Maintenance - Fix Soon, and Advisory according to the severity level; 1-6.
Severity 1 is the highest and 6 is the lowest level.
g) Click the Service Tools → Trends tab to display the device variables
(uncorrected volume flow rate, pressure and temperature) trends.
Field Device Specification manual
Installation manual
00825-0600-3104
for Commands
Gas Ultrasonic Flow Meters