Electrical installation
October 2023
Frequency output 1A is the A Phase of Frequency output 1 content (Uncorrected volume
flow rate, Corrected volume flow rate, Average flow velocity, Average speed of sound,
Energy flow rate, Mass flow rate)
Frequency output 1B is the B Phase of Frequency output 1
Frequency output 2A is the A Phase of Frequency output 2 content (Uncorrected volume
flow rate, Corrected volume flow rate, Average flow velocity, Average speed of sound,
Energy flow rate, Mass flow rate)
Frequency output 2B is the B Phase of Frequency output 2 content
Digital output 1A is based on Digital output1A content (Frequency Output 1Validity and
Flow Direction)
Digital output 1B is based on Digital output1B content (Frequency Output 1Validity and
Flow Direction)
Digital output 2A is based on Digital output 2A content (Frequency Output 1Validity and
Flow Direction)
Digital output 2B is based on Digital output 2B content (Frequency Output 1Validity and
Flow Direction)
Mode options
Open Collector (requires external excitation supply voltage and pull-up resistor)
TTL (internally powered by the meter 0-5 Vdc signal)
Channel B Phase options
Lag forward, Lead reverse (Phase B lags Phase A while reporting forward flow, leads
Phase A while reporting reverse flow)
Lead forward, Lag reverse (Phase B leads Phase A while reporting forward flow, lags
Phase A while reporting reverse flow)
Phase A and Phase B output (based on flow direction)
Reverse flow - output only reports flow in the reverse direction. For frequency outputs,
Phase B of the output is 90 degrees out of phase with Phase A.
Forward flow - output only reports flow in the forward direction. For frequency outputs,
Phase B of the output is 90 degrees out of phase with Phase A.
Absolute - output reports flow in both directions. For frequency outputs, Phase B of the
output is 90 degrees out of phase with Phase A.
Bidirectional - output reports flow on Phase A only in the forward direction and on
Phase B only in the reverse direction.
Maximum frequency for the frequency outputs
1000 Hz
5000 Hz
62
Installation manual
00825-0600-3104