Electrical installation
October 2023
Figure 3-18: CPU Module - Frequency/Digital outputs common ground - Type 4
A. FODO1 and DI1/FODO6: shared common ground - Type 4 CPU module (group 1)
B. FODO2, FODO3, FODO4, and FODO5: shared common ground - Type 4 CPU module
Analog input settings
The Rosemount 3410 Series Gas Ultrasonic Flow Meter has the capability to sample analog
temperature (Analog Input 1) and pressure (Analog Input 2) with 4-20 mA signals. These
analog input signals are configured to sink. The two independent analog input circuits are
configured for conventional 4-20 mA service. Also, 24 Vdc isolated power supply connection
is provided for an external power source. Refer to the Field wiring diagram DMC-005324 in
3410 Series engineering
Analog output settings
The Rosemount 3410 Series Ultrasonic Gas Flow Meter provides 4-20 mA analog output
signals that are software configurable for either sink or source current (see
engineering
Full HART
which meets the specifications of the HART Communications Foundation can be connected
to the Rosemount Gas Ultrasonic Flow Meter.
•
Analog Output 1 (AO1) is user-configurable as a 4-20 mA output and has HART
capabilities - Type 2 and Type 4 CPU Modules
•
Analog Output 2 (AO2) is user-configurable as a conventional 4-20 mA output - Type 2
CPU Module only
Digital input
The Rosemount 3410 Series Gas Ultrasonic Flow Meter provides one digital input that can
be used as a general purpose input. The digital input must be configured via the MeterLink
Tools|Edit → Compare Configuration screen.
64
(group 2)
drawings.
drawings, DMC-005324).
functionality is provided so that any commercially available HART transmitter
®
Installation manual
00825-0600-3104
3410 Series
Gas Ultrasonic Flow Meters