EGEA TECH

8.8.1 Remote connections

NOTE: for a CASCADE system, remote connections must be
made only on the MASTER.
Photovoltaic enabling
Verify that the following values are set:
P03=1 (see "3.9.9 Phv menu - EVU functionality - Photovoltaic functio-
nality" on page 146)
P04=offset (to be set, see "3.9.9 Phv menu - EVU functionality - Photo-
voltaic functionality" on page 146)
G01=0 (vedi "3.9.10 SG Menu - Smart Grid functionality (see also "8.8.1
Remote connections")" on page 147)
DIG2
Open
Normal operation
Closed
Operation in BOOST mode with Setpoint + Offset
EVU block enable
Verify that the following values are set:
P01=1 (see "3.9.9 Phv menu - EVU functionality - Photovoltaic functio-
nality" on page 146)
P02=mode with DIG1 input open (see "3.9.9 Phv menu - EVU functio-
nality - Photovoltaic functionality" on page 146)
G01=0 (see "3.9.10 SG Menu - Smart Grid functionality (see also "8.8.1
Remote connections")" on page 147)
In this configuration the water heater is subjected to an EVU
block by your electricity supplier.
DIG1
Open
Normal operation
Closed
Unit in Off / Standby (depending on parameter P02)
SMART GRID enabling
Verify that the following values are set:
G01=1 (see "3.9.10 SG Menu - Smart Grid functionality (see also "8.8.1
Remote connections")" on page 147
G02=operating state offset 3 (to be set, see "3.9.10 SG Menu - Smart
Grid functionality (see also "8.8.1 Remote connections")" on page 147)
When G01=1 is set, the water heater will work in SMART GRID mode
according to the 4 possible operating states:
DIG1
DIG2
Open
Closed
Open
Open
Closed
Open
Closed
Closed
NOTE The effect of the change of state of the di­
gital inputs DIG1 and DIG2 is applied after 10 min.
NOTA
200 HT - 260 HT
PV
EVU
Operational status
1
STANDBY unit
2
Operation in ECO mode
Operation in BOOST mode with
3
Setpoint + Offset
Operation in BOOST mode with
4
Setpoint max
cod. 3540000420 - Rev. 03 - 09/2023
Remote connection mode
For connection to the digital inputs, the equipment is equipped
with an additional 6-conductor cable (DIG1=EVU/SG0= white/
brown cable, DIG2=PV/SG1= green/yellow cable, DIG3= grey/
pink cable) already connected to the main -board (located inside
the device).
Remote connections to possible energy systems are the re-
sponsibility of the qualified installer (connection boxes, terminals
and connection cables).
The figures below give an example of a remote connection (fig.
67 and fig. 68), which must not be longer than 3 m.
fig. 67­ Remote connection example
fig. 68
EN
179