EGEA TECH
8.6

AERAULIC CONNECTIONS

In many images of this document
the position of the air ducts are
schematized at the top and bot­
ATTENZIONE
tom, in reality for the purposes
of correct installation we recom­
mend positioning the ducts side
by side (see fig. 51)
fig. 51– Arrangement of air channels

8.6.1 Standard aeraulic connections

In addition to the spaces indicated in section 8.4, the heat
pump requires adequate air ventilation.
• Create a dedicated air duct as indicated in fig. 52.
The simultaneous operation of
an open chamber fireplace (e.g.
open fireplace) and of the heat
ATTENZIONE
pump causes a dangerous nega­
tive pressure in the environment.
Mandatory air
inlet D.160 mm
fig. 52­ Example of air outlet connection
200 HT - 260 HT
Internal
compartment
cod. 3540000420 - Rev. 03 - 09/2023
Install each air duct making sure that:
• It does not weigh down on the equipment.
• It allows maintenance operations.
• It is adequately protected to prevent the accidental intrusion
of materials inside the equipment.
• The connection to the outside must be done with suitable,
non-flammable piping.
• The total equivalent length of the extraction pipes plus the
delivery, including grilles, must not exceed 12 m.
The table gives the characteristic data of commercial ducting
components with reference to nominal air flows and diameters
160 mm.
Smooth
Data
straight pipe
Type
Effective
1
length
Equivalent
1
length
• While operating, the heat pump tends to lower the tempera-
ture of the room if the air is not ducted outside.
• A suitable protection grille must be fitted during installation
near the external air exhaust pipe, to prevent foreign bodies
from getting inside the device. To ensure maximum product
performance, the grille must be selected from those with low
pressure loss.
• To prevent the formation of condensate: isolate the air ex-
haust pipes and the ducted air cover attachments with a va-
pour proof thermal coating of a suitable thickness.
• If necessary, install mufflers to prevent noise due to the air
flow. Fit the pipes, wall entries and connectors to the heat
pump systems with vibration damping.
Operating
hearth (e.g. open fireplace) and
the heat pump at the same time
ATTENTION
will cause a dangerous drop in
pressure in the room.
Smooth 90 °
Grille
curve
\
\
2
2
an
open­chamber
EN
UM
m
m
171