Maintenance; Disposal - Ferroli EGEA TECH 200 HT Manual

Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 128
EGEA TECH
Remember that refrigerant fluids
may be odorless.
OBLIGATION
The appliance must be installed,
operated and placed in an instal­
lation compartment with a mini­
OBLIGATION
mum height of no less than 2 me­
tres.
10.2

MAINTENANCE

Any
equipment must be performed by
qualified personnel. Exclusively
for interventions on the refrige­
ration circuit, including disposal,
the personnel must be equip­
ped with a suitable refrigeration
EXPERT TECHNI­
technician's license aimed at the
CIAN
knowledge and management of
systems containing gases of the
HFC type.
During maintenance operations, the operator in charge must
check the following points.
Installation conditions
Check that:
• The dimensions of the installation compartment are those
specified in this manual.
• Sufficient ventilation of the room is ensured.
• The markings and graphic signs on the product are present
and legible.
• There are no signs of damage or corrosion on the product that
could impair its operation or cause refrigerant gas to escape.
In case of differences in the product installation conditions,
maintenance personnel are required to inform the owner and
proceed with elimination of the non-conformities found.
Checks and repairs of electrical components
Check that:
• There are no conditions of imminent danger for the operator;
• The circuit is not powered.
• If it is not possible to operate without power supply, make
sure the owner has been notified regarding the situation.
• The electric capacitors have been safely discharged without
producing sparks.
200 HT - 260 HT
intervention
on
cod. 3540000420 - Rev. 03 - 09/2023
• There is continuity in the ground connection.
• The electrical components are replaced only with original
spare parts.
• No cuts or joints are made on the cables of the electrical com-
ponents.
• The cables and wires do not have any damage which could
compromise the integrity of the product and the safety of peo-
ple and/or property.
Note: only spare parts for original electrical components are
guaranteed by the manufacturer to be safe.
Search for refrigerant leaks
• Do not use any kind of flame to detect refrigerant leakage.
the
• Use electrical detectors only if you are sure of their efficiency
and safety.
• Alternatively, specific leak detector sprays can be used for re-
frigerant gases; the product used must be non-corrosive type.
In order to be used safely, the leak detection instruments must
have a calibration tool normally called a calibrated leak. Check-
ing the sensitivity of the detector with the aid of the calibration
tool must be carried out far from the place of installation in order
to ensurer correct calibration.

11. DISPOSAL

EXPERT
TECHNI­
CIAN
At the end of use, the heat pumps must be disposed of in com-
pliance with current regulations.
ATTENTION
Disposal operations must only be carried out at an authorised
centre by qualified personnel and in full compliance with current
regulations.
Before proceeding with the disposal of the product, it is neces-
sary to safely remove the refrigerant gas from the circuit; this op-
eration must be performed according to the following procedure:
Any intervention on the applian­
ce, including disposal, must be
carried out by qualified personnel
with a suitable refrigeration tech­
nician's license aimed at under­
standing and managing systems
containing HFC type gases.
Divide the materials and dispose
of them in special collection cen­
tres suitable for waste disposal,
according to the laws and regu­
lations in force in the country of
use.
EN
185

Advertisement

Table of Contents
loading

Table of Contents