6.1.3 Class ID 0x04 Assembly Objects

Table 24: Instance Attributes for Class ID 0x04 Assembly Objects
Instance
Access
Name
100
Set
[CTW], [REF]
130
Set
[STW], [MAV]
150
Get
Free configurable
180
Get
Free configurable
768
Set
Configuration
769
Set
Configuration

6.1.4 Class ID 0x06 Connection Manager

Table 25: Instance Attributes for Class ID 0x06 Connection Manager
Attribute
Access
Name
1
Get
Open requests
2
Get
Open format rejects
3
Get
Open resource rejects
4
Get
Open other rejects
5
Get
Close requests
6
Get
Close format requests
7
Get
Close other requests
8
Get
Connection timeouts

6.1.5 Class ID 0x47 DLR (Device Level Ring)

Table 26: Instance Attributes for Class ID 0x47 DLR (Device Level Ring)
Attribute
Access
Name
1
Get
Network topology
2
Get
Network status
10
Get
Active supervisor address
Supervisor IP address
Supervisor MAC address
36 | Danfoss A/S © 2023.09
Size
Description
4 bytes
Consuming assembly 100
80 bytes
Consuming assembly 130
4 bytes
Producing assembly 150
80 bytes
Producing assembly 180
4 bytes
Configuration assembly 769 (for instance 100, 150)
80 bytes
Configuration assembly 769 (for instance 130, 180)
Data type
Description
UINT
Number of forward open requests received.
UINT
Number of forward open requests rejected due to bad format.
UINT
Number of forward open requests rejected due to lack of resources.
UINT
Number of forward open requests rejected due to other reasons.
UINT
Number of forward close requests received.
UINT
Number of forward close requests rejected due to bad format.
UINT
Number of forward close requests rejected due to other reasons.
UINT
Number of connection timeouts.
Datatype
Description
USINT
Current network topology mode:
0 = Linear
1 = Ring
USINT
Status of network:
0 = Normal
1 = Ring fault
2 = Unexpected loop detected
3 = Partial network fault
4 = Rapid fault/restore cycle
Struct of:
UDINT
A Value of 0 indicates no IP Address has been configured for the
device
Ethernet MAC address
Array of 6
EtherNet/IP Features