Configuring Ethernet/Ip Scanner - Danfoss EtherNet/IP iC7 Series Operating Manual

Hide thumbs Also See for EtherNet/IP iC7 Series:
Table of Contents

Advertisement

iC7 Series EtherNet/IP
Operating Guide
Value
Fault
Warning - Change Con-
trol Place
Warning - Change Con-
trol Place – Persistent
Table 12: Control Place Descriptions
Value
Local control
Fieldbus control
I/O control
Advanced control

4.3 Configuring EtherNet/IP Scanner

Danfoss provides an electronic data sheet (EDS), which contains the necessary information for the offline configuration of
EtherNet/IP communication.
1.
Download the EDS files from
ware.
Each iC7 application requires its own EDS file. Check that the EDS file version is compatible with the firmware version.
2.
To configure a drive with EtherNet/IP for operation with a PLC system, install the EDS file.
Danfoss A/S © 2023.09
Description
The drive issues a fault, and coasts the motor.
The drive issues a warning. The control place changes to the selected alternative while timeout warn-
ing is active. The control place changes back to the original control place when fieldbus process data
returns.
The drive issues a warning. The control place changes to the selected alternative if timeout warning
is active. The control place requires a reset command to change back to the original control place
after fieldbus process data returns.
Description
The drive is controlled by a connected control panel.
The drive is controlled via a fieldbus.
The drive is controlled via I/O.
The drive is controlled via a combination of I/O and fieldbus.
www.danfoss.com/en/products/dds/low-voltage-drives/ic7-drives/ic7-automation/#tab-soft-
EtherNet/IP Configuration
AQ456329199699en-000101 / 136R0335 | 23

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ic7-automationIc7-baipEthernet/ip os7ip

Table of Contents