INSTALLER SETTING
152

Ceiling height setting (air conditioner)

It is the function to control the fan speed stage according to the ceiling height in the ceiling type
product.
• You can set the following setting values using [<,>(left/right)] button.
Ceiling height
Low
Fan speed operates one step slower than the default value.
Standard
Operates at the default fan speed
High
Fan speed operates one step faster than the default value.
Very high
Fan speed operates two steps faster than the default value.
NOTE
!
When group control is enabled some functions are limited depending on product type.
Description

Static pressure setting(air conditioner)

Static pressure setting can be set only in the duct products. (It cannot be set in other products.)
• You can set the following setting values using [<,>(left/right)] button.
Static pressure
Variable high static pressure
V-H
Fixed high static pressure
F-H
Variable low static pressure
V-L
Fixed low static pressure
F-L
• 2TH function's operation characteristics may be different for each product.
INSTALLER SETTING
Description
Variable / Fixed
ESP default value
Variable
High static pressure(High)
Fixed
High static pressure(High)
Variable
Low static pressure(Low)
Fixed
Low static pressure(Low)