INSTALLER SETTING
172
Occupancy duration time setting(air conditioner)
It is a function that sets the light-on/occupancy duration after motion is detected when installing
an occupancy sensor.
• You can set the following setting values using [<,>(left/right)] button.
0 Minute
10 Minutes
30 Minutes
60 Minutes
Value
CN_CC setting (air conditioner)
It is the function to set the usage of the indoor unit's CN_CC port.
• Select CN_CC setting category, and press [OK] button to move to the detail screen.
Value
When power is applied to the product, indoor unit when the contact
DC auto install
point is on in Dry Contact installed state recognizes Dry Contact
(default)
installation
DC manual not install Do not use (install) Dry Contact
DC manual install
Use (install) Dry Contact
Programmable DI/DO Use as Programmable DI/DO (Simple On/Off)
NOTE
!
CN_CC is the device connected to the indoor unit to recognize and control the external
contact point.
INSTALLER SETTING
173
OK
Description