INSTALLER SETTING
154
Remote controller master / slave setting
(air conditioner / General, DX ventilator)
This function sets configuration for the master/slave setting through the remote controller.
• Change setting values using [<,>(left/right)] button.
M/S
Using group control, the indoor units are operated based on the
Master (default)
remote controller.
Using group control, all remote controllers except 1 master remote
Slave
controller are set as slaves.
• 2TH function's operation characteristics may be different for each product.
Description
Override Master/Slave setting (air conditioner / General, DX
ventilator)
The operation master / slave selection function is to avoid other mode operations, and it is the
function to prevent the selection of opposite mode of the indoor unit master by the indoor units
set as slaves.
• Change setting values using [<,>(left/right)] button.
M/S
Master
Using group control, this master sets the mode of slave IDU's.
For the indoor unit set as slave, it can only select the some operation
mode of the master indoor unit cycle.
Ex) Master is in cooling cycle, Slave can select cooling,
Slave
dehumidification, auto, and wind only
Master is in heating cycle, Slave can select auto, heating, and wind
only
NOTE
!
Override M/S setting function is only available in some products.