Mounting; Basics - Siemens SIMATIC ET 200eco PN M12-L System Manual

Distributed i/o system et 200eco pn
Hide thumbs Also See for SIMATIC ET 200eco PN M12-L:
Table of Contents

Advertisement

Mounting

6.1

Basics

Introduction
All ET 200eco PN M12‑L distributed I/O devices are designed for IP65/IP67 and IP69K degrees
of protection. This means that you can directly mount these I/O devices in your plant. Only
use such accessories which are permitted for the required degree of protection.
Mounting position
You can mount the ET 200eco PN M12‑L distributed I/O devices in any mounting position.
Minimum clearances
Ensure that the I/O devices are installed with a minimum clearance of 2 cm.
If the installation distance to other devices or objects is less than 2 cm, the ambient
temperature must be reduced by 5 K (for example, 60 °C ⇒ 55 °C). This also applies to the
derating diagrams in the equipment manuals.
The plug cover is an accessory for protecting the connected connectors on the I/O device. The
plug cover may be necessary for use in hazardous areas. If you use the plug cover, the
minimum distances from section AUTOHOTSPOT apply.
Simple installation
The ET 200eco PN M12‑L distributed I/O devices are designed for easy installation.
• The I/O device should be mounted on a level solid surface.
• The I/O device can be pre-wired.
Mounting rules
When mounting the I/O device, you do not need to following any special rules.
The plug cover is an accessory for protecting the connected connectors on the I/O device. The
plug cover may be necessary for use in hazardous areas. If you use the plug cover, the
installation rules from section AUTOHOTSPOT apply.
NOTE
Mounting of the I/O devices
Install the ET 200eco PN M12‑L distributed I/O devices only with disconnected supply and
load voltages.
Distributed I/O system ET 200eco PN M12-L
System Manual, 11/2023, A5E48753295-AG
6
39